Performing <strong>Manual</strong> Control Section 4-13<br />

Related Displays and Parameters<br />

120<br />

The automatic display return function will not operate in manual mode.<br />

Balanceless-bumpless operation will be performed for the MV when<br />

switching between manual and automatic operation. (See note.)<br />

Switching between manual and automatic operation is possible for a<br />

maximum of one million times.<br />

When close control is used or when the Direct Setting of Position Proportional<br />

MV parameter is set to ON:<br />

Just as with standard models, the MV is set numerically.<br />

The automatic display return function will not operate in manual mode.<br />

Balanceless-bumpless operation will be performed for the MV when<br />

switching between manual and automatic operation. (See note.)<br />

Note In balanceless-bumpless operation, the MV before switching is<br />

used initially after the switch and then gradually changed to achieve<br />

the proper value after switch to prevent radical changes in the MV<br />

after switching operation.<br />

If a power interruption occurs during manual operation, manual operation<br />

will be restarted when power is restored using the same MV as when<br />

power was interrupted.<br />

Switching between manual and automatic operation is possible for a maximum<br />

of one million times.<br />

Operation will be as described below if a potentiometer input error occurs.<br />

When the <strong>Manual</strong> MV Limit Enable Parameter Is Set to OFF:<br />

<strong>Manual</strong> MV ≥ 100<br />

<strong>Manual</strong> MV ≤ 0<br />

If the manual MV is other than the above, the open and close outputs<br />

will both be OFF.<br />

When the <strong>Manual</strong> MV Limit Enable Parameter Is Set to ON:<br />

<strong>Manual</strong> MV = MV upper limit<br />

<strong>Manual</strong> MV = MV lower limit<br />

Open output: ON<br />

Close output: ON<br />

Open output: ON<br />

Close output: ON<br />

If the manual MV is other than the above, the open and close outputs<br />

will both be OFF.<br />

Parameter name Symbol Level Remarks<br />

PV/MV (<strong>Manual</strong> MV) --- <strong>Manual</strong> Control Level Changes the manual MV.<br />

Standard: −5.0 to 105.0 (See note 2.)<br />

Heating/cooling: −105.0 to 105.0 (See note 2.)<br />

Position-proportional: −5.0 to 105.0 (See notes 2<br />

and 3.)<br />

Direct Setting of Position<br />

Proportional MV<br />

pmvd Advanced Function Setting<br />

Level<br />

Selects the method for specifying each MV for<br />

manual operation, when stopping, or when an<br />

error occurs.<br />

OFF: All open, hold, all closed<br />

ON: −5.0 to 105%<br />

Auto/<strong>Manual</strong> Switch a-m Operation Level Switches between automatic and manual<br />

modes.<br />

Auto/<strong>Manual</strong> Select Addition<br />

amad Advanced Function Setting<br />

Level<br />

Enables switching between automatic and manual<br />

modes.<br />

Note (1) Refer to 4-17 Output Adjustment Functions for information on the priority<br />

for the MV.