Using the Transfer Output Section 4-14<br />

Transfer Output<br />

Destination<br />

Transfer Output Type<br />

The operation differs for models with a transfer output and models without<br />

a transfer output for which control output 1 or control output 2 is used as a<br />

simple transfer output, as shown in the following table.<br />

Transfer<br />

output<br />

Control output 1 Control output 2 Transfer output<br />

destination<br />

Yes --- --- Transfer output<br />

No Current output or linear None, relay output, voltage Control output 1<br />

voltage output output (for driving SSR), or<br />

SSR output<br />

No Current output or linear Current output or linear Control output 1<br />

voltage output voltage output<br />

No Relay output, voltage Current output or linear Control output 2<br />

output (for driving<br />

SSR), or SSR output<br />

voltage output<br />

No Relay output, voltage None, relay output, voltage None<br />

output (for driving output (for driving SSR), or<br />

SSR), or SSR output SSR output<br />

■ Precision and User Calibration<br />

Precision User calibration<br />

Transfer output ±0.3% FS Supported. (See note.)<br />

Simple transfer output<br />

Not specified. Not supported.<br />

Note For details on the calibration method, refer to SECTION 6 CALI-<br />

BRATION.<br />

Transfer output type Symbol Setting range<br />

OFF (See note 1.) off ---<br />

Set point sp SP lower limit to SP upper limit<br />

Set point during SP ramp sp-m SP lower limit to SP upper limit<br />

PV pv Input setting range lower limit to input setting<br />

range upper limit or<br />

Scaling lower limit to scaling upper limit<br />

MV monitor (heating) mv −5.0 to 105.0 (heating/cooling control: 0.0 to<br />

(See note 4.)<br />

105.0) (See note 2.)<br />

MV monitor (cooling)<br />

(See note 5.)<br />

c-mv 0.0 to 105.0 (See note 2.)<br />

Valve opening (See note<br />

6.)<br />

v-m −10.0 to 110.0<br />

Note (1) The default is OFF. For a Controller that does not support a transfer output,<br />

the item specified for the Control Output 1 Assignment or Control<br />

Output 2 Assignment parameter will be output.<br />

(2) The output value will be different between when the Transfer Output Type<br />

parameter is set to MV monitor (heating) or MV monitor (cooling), and<br />

when the Control Output 1 Assignment parameter is set to a heating control<br />

output or cooling control output.<br />

Example: When a Current Output Is Set to 4 to 20 mA and MV Monitor<br />

(Heating) Is Selected<br />

When used as a transfer output, 4.0 mA will be output for 0% and<br />

20.0 mA will be output for 100%.<br />

125