Adjustment Level Section 5-4<br />

See<br />

■ Related Parameters<br />

oc1 Heater Overcurrent Detection 1<br />

Function<br />

Setting<br />

See<br />

Heater current 1 value monitor (adjustment level): Page 181<br />

HB ON/OFF, Heater burnout latch, Heater burnout hysteresis (advanced function<br />

setting level): Page 246, 247<br />

Heater burnout, HS alarms, and<br />

heater overcurrent detection must be<br />

supported.<br />

Alarm 1 must be assigned.<br />

The Heater Overcurrent Use ON/<br />

OFF parameter must be set to ON.<br />

This parameter sets the current value for heater overcurrent alarm outputs.<br />

A heater overcurrent alarm is output when the heater current exceeds the<br />

value set for this parameter.<br />

When the set value is 50.0, the heater overcurrent alarm is turned OFF.<br />

When the set value is 0.0, the heater overcurrent alarm is turned ON.<br />

Setting range Unit Default<br />

0.0 to 50.0 A 50.0<br />

■ Related Parameters<br />

Heater current 1 value monitor (adjustment level): Page 181<br />

Heater overcurrent use, Heater overcurrent latch, Heater overcurrent hysteresis<br />

(advanced function setting level): Page 272, 273<br />

ct2 Heater Current 2 Value Monitor<br />

Function<br />

Monitor<br />

Heater burnout, HS alarms, and<br />

heater overcurrent detection must be<br />

supported (two CTs).<br />

Alarm 1 must be assigned.<br />

The HB ON/OFF or Heater Overcurrent<br />

Use parameter must be set to<br />

ON.<br />

This parameter measures the heater current from the CT input used for<br />

detecting heater burnout.<br />

This parameter measures and displays the heater current value.<br />

Heater burnouts and heater overcurrent are not detected if the control<br />

output (heating) ON time is 100 ms or less.<br />

Monitor range Unit<br />

0.0 to 55.0 A<br />

ffff is displayed when 55.0 A is exceeded.<br />

If a heater burnout detection 2 or heater overcurrent detection 2 alarm is<br />

output, the HA indicator will light and the No. 1 display for the heater current<br />

2 value monitor will flash.<br />