Transfer Output<br />

Lower Limit<br />

Linear Current Output<br />

Appendix<br />

Parameters Characters Setting (monitor) value Display Default Unit Set value<br />

tr-l See note 6. See note 6. See note 6.<br />

o1-t 4-20: 4 to 20 mA<br />

0-20: 0 to 20 mA<br />

Bank Numbers Used ev-b 0 to 2<br />

0 to 3 (Only when four event<br />

inputs are supported)<br />

Event Input Assignment<br />

1<br />

Event Input Assignment<br />

2<br />

Event Input Assignment<br />

3<br />

Event Input Assignment<br />

4<br />

ev-1 None: None<br />

STOP: RUN/STOP<br />

MANU: Auto/<strong>Manual</strong><br />

PRST: Program Start (See<br />

note 3.)<br />

DRS: Invert Direct/Reverse<br />

Operation<br />

AT-2: 100% AT Execute/Cancel<br />

AT-1: 40% AT Execute/Cancel<br />

WTPT: Setting Change<br />

Enable/Disable<br />

CMWT: Communications<br />

Write Enable/Disable<br />

LAT: Alarm Latch Cancel<br />

ev-2 None: None<br />

STOP: RUN/STOP<br />

MANU: Auto/<strong>Manual</strong><br />

PRST: Program Start (See<br />

note 3.)<br />

DRS: Invert Direct/Reverse<br />

Operation<br />

AT-2: 100% AT Execute/Cancel<br />

AT-1: 40% AT Execute/Cancel<br />

WTPT: Setting Change<br />

Enable/Disable<br />

CMWT: Communications<br />

Write Enable/Disable<br />

LAT: Alarm Latch Cancel<br />

ev-3 Same as for Event Input<br />

Assignment 1.<br />

ev-4 Same as for Event Input<br />

Assignment 1.<br />

Closed/Floating clfl FLOT: Floating<br />

CLOS: Closed<br />

4-20, 0-20 4-20 None<br />

none<br />

stop<br />

manu<br />

prst<br />

1 None<br />

Note (1) Displayed when there is a remote SP input.<br />

(2) If the PV is selected, the remote SP will be output as long as the SP Mode is set to the Remote SP<br />

Mode.<br />

(3) This setting is ignored for position-proportional control models.<br />

(4) This setting is ignored for models with standard or position-proportional control.<br />

(5) Displayed only when there is a potentiometer input for a model with position-proportional control.<br />

drs<br />

at-2<br />

at-1<br />

wtpt<br />

cmwt<br />

lat<br />

none<br />

stop<br />

manu<br />

prst<br />

drs<br />

at-2<br />

at-1<br />

wtpt<br />

cmwt<br />

NONE None<br />

STOP None<br />

lat<br />

none NONE None<br />

none NONE None<br />

flot,<br />

clos<br />

FLOT None<br />

Motor Calibration calb OFF, ON off,<br />

on<br />

OFF None<br />

Travel Time mot 1 to 999 30 s<br />

Extraction of Square<br />

Root Enable<br />

Move to Advanced<br />

function Setting<br />

Level<br />

sqr OFF, ON off,<br />

on<br />

OFF None<br />

amov −1999 to 9,999 0 None<br />

321