Adjustment Level Section 5-4<br />

cmwt Communications Writing<br />

Function<br />

Setting<br />

See<br />

This parameter enables/disables writing of parameters to the <strong>Digital</strong> <strong>Controllers</strong><br />

from the host (personal computer) using communications.<br />

This parameter is not displayed if communications write enable/disable is<br />

set for execution using an event input assignment 1 to 4.<br />

ON: Writing enabled<br />

OFF: Writing disabled<br />

Default: OFF<br />

■ Related Parameters<br />

MB command logic switching (advanced function setting level): Page 252<br />

Communications unit No., Communications baud rate, Communications data<br />

length, Communications parity, Communications stop bits (communications<br />

setting level): Page 281<br />

irdr Infrared Communications Use<br />

Function<br />

Setting<br />

spmd SP Mode<br />

Function<br />

Setting<br />

This parameter enables or disables infrared communications between the<br />

host (personal computer) and the <strong>Digital</strong> Controller.<br />

Set this parameter to ON only when connecting to a Setup Tool, and leave<br />

it set to OFF during normal operation.<br />

ON: Infrared communications enabled.<br />

OFF: Infrared communications disabled.<br />

Default: OFF<br />

Communications must be supported.<br />

The Event Input Assignments 1 to 4<br />

parameters must not be set to<br />

enable communications writing.<br />

Infrared communications must be<br />

supported.<br />

The ST parameter must be set to<br />

OFF.<br />

The Remote SP Enable parameter<br />

must be set to ON.<br />

The Event Input Assignment 1 to 4<br />

parameters must not be set to switch<br />

to SP mode.<br />

This parameter is used to select the SP mode.<br />

In Local SP Mode, the local SP set in bank is used as the target value in<br />

the control operation. In Remote SP Mode, the remote SP set via an<br />

external signal (e.g., 4 to 20 mA) is used as the target value in the control<br />

operation.<br />

Setting range Default<br />

RSP: Remote SP, LSP: Local SP LSP<br />

193