Scaling Upper Limit in-h Scaling lower limit + 1 to<br />

32400<br />

100 None<br />

Scaling Lower Limit in-l −19,999 to scaling upper limit<br />

−1<br />

0 None<br />

Decimal Point dp 0 to 3 0 None<br />

Temperature Unit d-u °C, °F c, f °C None<br />

SP Upper Limit sl-h Temperature input: SP lower<br />

limit + 1 to input range upper<br />

limit<br />

Analog input: SP lower limit +<br />

1 to Scaling upper limit<br />

1300.0 EU<br />

SP Lower Limit sl-l Temperature input: Input<br />

range lower limit to SP upper<br />

limit −1<br />

Analog: Scaling lower limit to<br />

SP upper limit −1<br />

−200.0 EU<br />

PID ON/OFF cntl ON/OFF 2-PID onof, pid PID None<br />

Standard or Heating/<br />

Cooling<br />

s-hc Standard or heating/cooling send, h-c Standard None<br />

ST st OFF, ON off, on ON None<br />

Program Pattern ptrn OFF, STOP, CONT, LOOP off, stop,<br />

cont<br />

OFF None<br />

Valid Program Bank pbnk 0 to 7 7 None<br />

Control Period<br />

(Heating)<br />

cp 0.5 or 1 to 99 0.5, 1 to 99 20 Second<br />

Control Period (Cooling)<br />

c-cp 0.5 or 1 to 99 0.5, 1 to 99 20 Second<br />

Appendix<br />

Parameters Characters Setting (monitor) value Display Default Unit Set value<br />

Direct/Reverse<br />

Operation<br />

orev Reverse operation, direct<br />

operation<br />

or-r, or-d Reverse<br />

operation<br />

None<br />