Setting the SP Upper and Lower Limit Values Section 4-6<br />

Switching Setting<br />

Change Enable/<br />

Disable<br />

Switching<br />

Communications<br />

Write Enable/Disable<br />

Switching Alarm<br />

Latch Cancel<br />

Parameters<br />

100<br />

When WTPT (Setting Change Enable/Disable) is set for either the Event Input<br />

Assignment 1 or Event Input Assignment 2 parameter, the setting change will<br />

be disabled when event input 1 or 2 turns ON and will be enabled when the<br />

input turns OFF.<br />

Only event inputs 3 and 4 can be set to Communications Write Enable/Disable.<br />

When CMWT (Communications Write Enable/Disable) is set for either the<br />

Event Input Assignment 3 or Event Input Assignment 4 parameter, communications<br />

writing will be enabled when event input 3 or 4 turns ON and will be<br />

disabled when the input turns OFF.<br />

When LAT (Alarm Latch Cancel) is set for either the Event Input Assignment 1<br />

or Event Input Assignment 2 parameter, all alarm latches (alarms 1 to 3,<br />

heater burnout, HS alarm, and heater overcurrent latch) will be cancelled<br />

when event input 1 or 2 turns ON.<br />

4-6 Setting the SP Upper and Lower Limit Values<br />

4-6-1 Set Point Limiter<br />

Setting Input contact Status<br />

Event input 1 or 2 OFF Enabled<br />

Event input 1 or 2 ON Disabled<br />

Setting Input contact Status<br />

Event input 3 or 4 OFF Disabled<br />

Event input 3 or 4 ON Enabled<br />

Setting Input contact Status<br />

Event input 1 or 2 OFF ---<br />

Event input 1 or 2 ON Cancelled<br />

Symbol Parameter: level Description<br />

ev-1 Event Input Assignment 1: Initial setting level Function of<br />

ev-2<br />

ev-3<br />

Event Input Assignment 2: Initial setting level<br />

Event Input Assignment 3: Initial setting level<br />

event input function<br />

ev-4 Event Input Assignment 4: Initial setting level<br />

ev-b Bank Numbers Used: Initial setting level<br />

The setting range of the set point is limited by the set point limiter. The set<br />

point limiter is used to prevent the control target from reaching abnormal temperatures.<br />

The upper- and lower-limit values of the set point limiter are set<br />

using the Set Point Upper Limit and Set Point Lower Limit parameters in the<br />

initial setting level. When the set point limiter is reset, the set point is forcibly<br />

changed to the upper- or lower-limit value of the set point limiter if the set point<br />

is out of the limiter range. Also, when the input type and the temperature unit,<br />

scaling upper-limit value, or lower-limit value are changed, the set point limiter<br />

is forcibly reset to the input setting range or the scaling upper- or lower-limit<br />

value.