Thermocouple Calibration (Thermocouple/Resistance Thermometer Input) Section 6-3<br />

In this example, calibration is shown for a Controller with a thermocouple set<br />

as the input type.<br />

1,2,3... 1. Connect the power supply.<br />

2. Connect a standard DC current/voltage source (STV), precision digital<br />

multimeter (DMM), and contact junction compensator (e.g., a zero controller<br />

as in the figure) to the thermocouple input terminals, as shown in<br />

the figure below.<br />

STV<br />

DMM<br />

Leave open.<br />

Zero<br />

controller<br />

OUTPUT INPUT<br />

3. Turn the power ON.<br />

adj<br />

30<br />

4. Move to the calibration level.<br />

This starts the 30-minute aging timer. This timer provides an approximate<br />

timer for aging. After 30 minutes have elapsed, the No. 2 display changes<br />

to 0. You can advance to the next step in this procedure even if 0 is not<br />

displayed.<br />

Input types 5, 7, 11, 12, 15, 19, 20: 5. When the M Key is pressed, the status changes as shown to the left.<br />

t-54<br />

The No. 2 display at this time shows the currently entered count value in<br />

hexadecimal. Set the STV as follows:<br />

b9a5<br />

Input types 5, 7, 11, 12, 15, 19, 20: Set to 54 mV.<br />

Input types 6, 8, 9, 10, 13, 14, 16,<br />

17, 18, 21, 22, 23:<br />

t-24<br />

e220<br />

Input types 6, 8, 9, 10, 13, 14, 16, 17, 18, 21, 22, 23:<br />

Set to 24 mV.<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

t--6<br />

2988<br />

6. When the M Key is pressed, the status changes as shown to the left.<br />

Set the STV to −6 mV.<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

c700 -<br />

ba13<br />

7. Press the M Key. The display changes as shown on the left. Set the STV<br />

to 700 mV.<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

−<br />

+<br />

Compensating conductor of currently selected<br />

thermocouple<br />

Use K thermocouple compensating conductor<br />

for E, R, S, B, W, and PLII thermocouples.<br />

287