Output Adjustment Functions Section 4-17<br />

4-17-3 MV at PV Error<br />

If the Direct Setting of Position Proportional MV parameter is set to ON during<br />

close control, the valve opening can be specified. The default setting is 0.0<br />

(i.e., the open and close outputs are adjusted so that valve opening will be 0).<br />

Parameter<br />

name<br />

Setting range Unit Default<br />

MV at STOP −5.0 to 105.0 for standard control<br />

−105.0 to 105.0 (heating/cooling control)<br />

Position-proportional Control<br />

Close control and Direct Setting of Position<br />

Proportional MV parameter ON: −5.0<br />

to 105.0<br />

Floating control or Direct Setting of Position<br />

Proportional MV parameter OFF:<br />

CLOS (Control output 2 ON)<br />

HOLD (Control outputs 1 and 2 both<br />

OFF)<br />

OPEN (Control output 1 ON)<br />

% or none 0.0 or HOLD<br />

Note The order of priority is as follows: <strong>Manual</strong> MV > MV at stop > MV at PV error.<br />

The following table shows the operation when a potentiometer error<br />

occurs when the Direct Setting of Position Proportional MV parameter is<br />

set to ON.<br />

MV at stop ≥ 100<br />

MV at stop ≤ 0<br />

Open output ON<br />

Close output ON<br />

When the MV at stop is other than the above, the open and close outputs<br />

will both be OFF.<br />

A fixed MV is output for an input error, RSP input error, or potentiometer<br />

error (close control only). To set the MV at PV error, set the MV at Stop<br />

and Error Addition parameter (advanced function setting level) to ON.<br />

The MV at stop takes priority when stopped and the manual MV takes priority<br />

in manual mode.<br />

■ Standard Models<br />

With heating/cooling control, the MV on the cooling side is taken to be a negative<br />

value, so the output is made to the heating side for a positive value and<br />

to the cooling side for a negative value. The default setting is 0.0 (i.e., there<br />

are not outputs for either standard control or heating/cooling control).<br />

■ Position-proportional Models<br />

Open, close, or hold status can be selected for floating control or when the<br />

Direct Setting of Position Proportional MV parameter is set to OFF. With open<br />

status, only the open output will turn ON. With close status, only the close output<br />

will turn ON. With hold status, the open and close outputs will both turn<br />

OFF. The default setting is for hold status, with no outputs.<br />

143