Setting the PF Key Section 4-20<br />

Set<br />

Setting Remarks<br />

value<br />

Monitor/Setting Symbol<br />

0 Disabled ---<br />

1 PV/SP/Bank No. (See note 1.) Can be set. (SP) ---<br />

2 PV/SP/MV (See notes 1 and 2.) Can be set. (SP) ---<br />

3 PV/SP /Soak time remain (See note 1.) Can be set. (SP) ---<br />

4 Proportional band (P) (See note 3.) Can be set. p<br />

5 Integral time (I) (See note 3.) Can be set. i<br />

6 Derivative time (D) (See note 3.) Can be set. d<br />

7 Alarm value 1 (See note 4.) Can be set. al-1<br />

8 Alarm value upper limit 1 (See note 4.) Can be set. al1h<br />

9 Alarm value lower limit 1 (See note 4.) Can be set. al1l<br />

10 Alarm value 2 (See note 4.) Can be set. al-2<br />

11 Alarm value upper limit 2 (See note 4.) Can be set. al2h<br />

12 Alarm value lower limit 2 (See note 4.) Can be set. al2l<br />

13 Alarm value 3 (See note 4.) Can be set. al-3<br />

14 Alarm value upper limit 3 (See note 4.) Can be set. al3h<br />

15 Alarm value lower limit 3 (See note 4.) Can be set. al3l<br />

16 Bank No. Can be set. bank<br />

Note (1) The SP for the current bank will be displayed.<br />

(2) For details on MV settings for heating and cooling control, refer to MV<br />

Display for Heating and Cooling Control on page 82.<br />

(3) The set value for the current PID set will be displayed.<br />

(4) The set value for the current bank will be displayed.<br />

Setting Monitor/Setting Items<br />

Pressing the PF Key in the operation, adjustment, bank setting, or PID setting<br />

level displays the applicable monitor/setting items. Press the PF Key to display<br />

in order Monitor/Setting Items 1 to 5. After Monitor/Setting Item 5 has<br />

been displayed, the display will switch to the top parameter in the operation<br />

level.<br />

Note (1) Items set as disabled in the Monitor/Setting Items 1 to 5 parameters will<br />

not be displayed, and the display will skip to the next enabled setting.<br />

(2) While a monitor/setting item is being displayed, the display will be<br />

switched to the top parameter in the operation level if the M Key or the<br />

O Key is pressed.<br />

Operating Procedure This procedure sets the PF Setting parameter to PFDP, and the Monitor/Setting<br />

Item 1 parameter to 7 (Alarm Value 1).<br />

Operation Level<br />

C<br />

PV/SP<br />

25.0<br />

100.0<br />

Initial Setting Level 1. Press the O Key for at least three seconds to move from the operation<br />

Input Type<br />

level to the initial setting level.<br />

in-t 5<br />

149