Using Banks and PID Sets Section 4-15<br />

4-15 Using Banks and PID Sets<br />

Banks Up to eight banks, each of which contains the following parameters, can be<br />

created. The current bank number can be changed by using key operations,<br />

event inputs, communications (operation commands), or simple programs.<br />

PID Set Number<br />

PID Set No.<br />

0.pid 1<br />

Parameter 0 1 • • • 7<br />

Set Point 200.0 500.0<br />

PID Set No. 0 0<br />

SP Ramp Set Value OFF OFF<br />

Alarm Value 1 to 3 240.0 300.0<br />

Alarm Value Upper Limit<br />

1 to 3<br />

40.0 30.0<br />

Alarm Value Lower Limit<br />

1 to 3<br />

40.0 30.0<br />

Soak Time 5 10<br />

Wait Band 3.0 5.0<br />

In the bank setting level, select the bank numbers to be edited with the Display<br />

Bank Selection parameter, and make the settings for each bank.<br />

Parameter Setting<br />

range<br />

Unit Default<br />

Bank No. 0 to 7 --- 0<br />

Display Bank Selection 0 to 7 --- See note.<br />

Note The current bank will be displayed. If you change the bank using<br />

the U and D Keys, monitor function will be canceled.<br />

If the following parameters are changed, the changes will be saved in the current<br />

bank:<br />

Set Point, Alarm Values 1 to 3, Alarm Value Upper Limits 1 to 3, Alarm Value<br />

Lower Limits 1 to 3, (operation level)<br />

SP Ramp Set Value, Soak Time, Wait Band (adjustment level).<br />

Select a number from 1 to 8 to specify the PID set for each bank.<br />

The default setting is 1. For details, refer to PID Sets.<br />

The bank number can be confirmed by checking the number at the<br />

beginning of the parameter.<br />

Simple Program and Bank Functions<br />

For each bank, the Soak Time and Wait Band parameters can be set, and a<br />

simple program can be created. For details on creating a simple program,<br />

refer to 4-16 Using the Simple Program Function.<br />

PID Sets The PID set to be executed is selected by using the PID Set No. parameter<br />

in the bank setting level. If 0 (Automatic selection) is set, then the PID<br />

set will be selected automatically according to preset conditions.<br />

Up to eight of the following parameters can be registered for each PID set.<br />

Parameter Setting range Default Unit<br />

Proportional Band Temperature: 0.1 to 3,240.0 8.0 °C or °F<br />

Analog: 0.1 to 999.9 10.0 %FS<br />

129