05.03.2013 Views

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Logic Operations Section 4-25<br />

<strong>Manual</strong> Operation<br />

MV at Stop and Error<br />

4-25 Logic Operations<br />

With models that support position-proportional control, manual operation is<br />

possible by moving to the manual control level and pressing the Up and Down<br />

Keys. The output on the open side is ON while the Up Key is pressed, and the<br />

output on the closed side is ON while the Down Key is pressed. If the Direct<br />

Setting of Position Proportional MV parameter is set to ON and closed control<br />

is used, however, the <strong>Manual</strong> MV parameter can be set with the same display<br />

and operations as for standard models.<br />

With floating control or when the Direct Setting of Position Proportional MV<br />

parameter is set to OFF, select to output open, closed, or hold status when<br />

stopped or when an error occurs. If the Direct Setting of Position Proportional<br />

MV parameter is set to ON for closed control, set the MV.<br />

4-25-1 The Logic Operation Function (CX-Thermo)<br />

4-25-2 Using Logic Operations<br />

Starting Logic<br />

Operations<br />

The logic operation function logically calculates as 1 or 0 the Controller<br />

status (alarms, SP ramp, RUN/STOP, auto/manual, etc.) and the external<br />

event input status, and outputs the results to work bits. The work bit status<br />

can be output to auxiliary or control outputs, and operating status can be<br />

switched according to the work bit status.<br />

Work bit logic operation can be set from 1 to 8. Set them to No operation<br />

(Always OFF) (the default) when the work bits are not to be used. When<br />

logic operations are being used, a dot will be displayed on the No. 2 display<br />

of the adjustment level display<br />

Adjustment Level<br />

Adjustment level display<br />

l.adj<br />

.<br />

Dot displayed.<br />

Logic operations are set using the CX-Thermo.<br />

There are two ways to start logic operations.<br />

Select Logic Operation Editor from the CX-Thermo tree, and click the<br />

Start Button.<br />

159

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!