Alarm Hysteresis Section 4-2<br />

For example, with a lower limit alarm, the process value will normally be<br />

below the set point, i.e., within the alarm range, when the power supply is<br />

turned ON, causing an alarm to be output.<br />

If the lower limit alarm with a standby sequence is selected, an alarm will<br />

not be output until the process value increases above the alarm set value,<br />

i.e., until it leaves the alarm range, and then falls back below the alarm set<br />

value.<br />

Restart The standby sequence is canceled when an alarm is output. It is, however,<br />

restarted later by the Standby Sequence Reset parameter<br />

(advanced function setting level). For details, refer to the Standby<br />

Sequence Reset parameter in SECTION 5 Parameters.<br />

4-2-2 Alarm Latch<br />

Summary of Alarm<br />

Operation<br />

Parameters<br />

The alarm latch can be used to keep the alarm output ON until the latch is<br />

canceled regardless of the temperature once the alarm output has turned<br />

ON.<br />

Any of the following methods can be used to clear the alarm latch.<br />

Turn OFF the power supply. (The alarm latch is also cleared by switching<br />

to the initial setting level, communications setting level, advanced function<br />

setting level, or calibration level.)<br />

Use the PF Key.<br />

Use an event input.<br />

For details on setting the PF Key, refer to 4-20 Setting the PF Key. For details<br />

on setting events, refer to 4-5 Using Event Inputs.<br />

The following figure summarizes the operation of alarms when the Alarm Type<br />

parameter is set to “lower-limit alarm with standby sequence” and “close in<br />

alarm” is set.<br />

Alarm value<br />

Alarm<br />

Note * = 1 to 3<br />

Alarm type: Lower-limit alarm with standby sequence<br />

PV<br />

Standby sequence<br />

canceled<br />

Alarm hysteresis<br />

Time<br />

ON<br />

OFF<br />

ON (closed)<br />

Output OFF (open)<br />

Symbol Parameter: level Description<br />

alh*<br />

rest<br />

Alarm 1 to 3 Hysteresis: Initial setting level<br />

Standby Sequence: Advanced function setting level<br />

Alarm<br />

Alarm<br />

91