Determining PID Constants (AT, ST, <strong>Manual</strong> Setup) Section 3-8<br />

AT Calculated Gain<br />

The AT Calculated Gain parameter sets the gain for when PID values are calculated<br />

using AT. When emphasizing response, decrease the set value. When<br />

emphasizing stability, increase the set value.<br />

AT Hysteresis<br />

The AT Hysteresis parameter sets the hysteresis when switching ON and OFF<br />

for the limit cycle operation during auto-tuning.<br />

Limit Cycle MV Amplitude<br />

The Limit Cycle MV Amplitude parameter sets the MV amplitude for limit cycle<br />

operation during auto-tuning.<br />

Note Disabled for 100% AT.<br />

■ 40% AT<br />

The width of MV variation in the limit cycle can be changed in the Limit Cycle<br />

MV Amplitude parameter, but the AT execution time may be longer than for<br />

100% AT. The limit cycle timing varies according to whether the deviation (DV)<br />

at the start of auto-tuning execution is less than 10% FS.<br />

PV<br />

SP<br />

Deviation ≥ 10% FS<br />

Deviation:<br />

10% FS<br />

Limit Cycle MV<br />

Amplitude 40%<br />

AT started AT ended<br />

Time<br />

■ 100% AT<br />

Operation will be as shown in the following diagram, regardless of the deviation<br />

(DV) at the start of AT execution. To shorten the AT execution time, select<br />

100% AT.<br />

Operating Procedure This procedure executes 100%AT.<br />

PV<br />

SP<br />

AT started AT ended<br />

Deviation < 10% FS<br />

Note The Limit Cycle MV Amplitude parameter is disabled.<br />

PV<br />

SP<br />

Deviation:<br />

10% FS<br />

Limit Cycle MV<br />

Amplitude 40%<br />

AT started AT ended<br />

Limit Cycle MV<br />

Amplitude 100%<br />

Adjustment Level 1. Press the O Key to move from the operation level to the adjustment level.<br />

AT Execute/<br />

Cancel<br />

Press the M Key to select the AT Execute/Cancel parameter.<br />

at<br />

off<br />

at<br />

at-2<br />

Time<br />

Time<br />

2. Press the U Key to select at-2. The No. 1 display for AT Execute/Cancel<br />

will flash during AT execution.<br />

61