Setting the No. 3 Display Section 3-11<br />

Operating Procedure This procedure displays PV/SP/MV and PV/SP/Bank No. on the Process<br />

Value/Set Point display. The PV/SP Display Screen Selection parameter is set<br />

to 2.<br />

Operation Level 1. Press the O Key for at least three seconds to move from the operation<br />

PV/SP<br />

level to the initial setting level.<br />

C<br />

25.0<br />

100.0<br />

50.0<br />

Initial Setting Level 2. Press the M Key to select the Move to Advanced Function Setting Level<br />

Input Type<br />

in-t<br />

5<br />

parameter.<br />

Initial Setting Level 3. Use the D Key to enter the password (“−169”).<br />

amov<br />

-169<br />

It is possible to move to the advanced function setting level by either<br />

pressing the M Key or waiting two seconds without pressing any key.<br />

Advanced Function Setting Level 4. Press the M Key to select the PV/SP Display Screen Selection parame-<br />

Parameter<br />

init Initialization<br />

off<br />

ter.<br />

Advanced Function Setting Level 5. Use the U and D Keys to set 2.<br />

6. Press the O Key for at least one second to move from the advanced<br />

function setting level to the initial setting level.<br />

Initial Setting Level 7. Press the O Key for at least one second to move from the initial setting<br />

Input Type<br />

in-t<br />

5<br />

level to the operation level.<br />

The MV will be displayed on the No. 3 display.<br />

Operation Level 8. Press the M Key to confirm that the Bank No. is displayed on the No. 3<br />

C<br />

spdp 4<br />

spdp 2<br />

Operation Level<br />

C<br />

25.0<br />

100.0<br />

50.0<br />

25.0<br />

100.0<br />

b.0<br />

Move to<br />

Advanced<br />

Function Setting<br />

Level<br />

PV/SP Display<br />

Screen Selection<br />

PV/SP<br />

PV/SP<br />

83