Determining PID Constants (AT, ST, <strong>Manual</strong> Setup) Section 3-8<br />

3-8 Determining PID Constants (AT, ST, <strong>Manual</strong> Setup)<br />

3-8-1 AT (Auto-tuning)<br />

60<br />

at<br />

When AT is executed, the optimum PID constants for the set point at that<br />

time are set automatically. A method (called the limit cycle method) for<br />

forcibly changing the manipulated variable and finding the characteristics<br />

of the control object is employed.<br />

Either 40% AT or 100% AT can be selected depending on the width of MV<br />

variation in the limit cycle. In the AT Execute/Cancel parameter, specify<br />

at-2 (100% AT) or at-1 (40% AT). To cancel AT, specify off (AT cancel).<br />

Only 100% AT can be executed for heating and cooling control or for floating<br />

control for position-proportional models.<br />

AT cannot be executed when control has stopped or during ON/OFF control.<br />

The results of AT are reflected in the Proportional Band (P), Integral Time<br />

(I), and Derivative Time (D) parameters for the PID set at the time AT execution<br />

starts. For details on PID sets, refer to PID Sets on page 129.<br />

PID Setting Level<br />

C<br />

PID* Proportional Band<br />

∗.p (0<br />

∗.i<br />

233.0<br />

∗.d<br />

40.0<br />

AT Operations AT is started when either at-2 (100% AT) or at-1 (40% AT) is specified for<br />

the AT Execute/Cancel parameter. During execution, the AT Execute/Cancel<br />

parameter on the No. 1 display flashes. When AT ends, the AT Execute/Cancel<br />

parameter turns OFF, and the No. 1 display stops flashing.<br />

AT Execute/Cancel<br />

PID* Integral Time<br />

PID* Derivative Time<br />

at<br />

off<br />

(∗ : 1 to 8)<br />

at<br />

at-2<br />

If you move to the operation level during AT execution, the No. 2 display<br />

flashes to indicate that AT is being executed.<br />

PV/SP<br />

C<br />

25.0<br />

100.0<br />

100% AT execution in progress<br />

No. 1 display<br />

Only the Communications Writing, RUN/STOP, AT Execution/Cancel, and Program<br />

Start parameters can be changed during AT execution. Other parameters<br />

cannot be changed.<br />

C<br />

25.0<br />

100.0<br />

AT execution in progress<br />

No. 2 display