Logic Operations Section 4-25<br />

164<br />

(2) Turns ON when either the control output 1 or 2 ON/OFF count alarm is<br />

ON.<br />

5. Switching between Normally Open and Normally Closed for Inputs A to D<br />

Click the condition to switch between normally open and normally closed<br />

inputs A to D.<br />

Normally open Normally closed<br />

6. Switching between Normally Open and Normally Closed for Work Bits<br />

Click the condition to switch between normally open and normally closed<br />

work bits.<br />

Normally open Normally closed<br />

7. Setting ON Delay Times<br />

When an input with an ON delay turns ON, the output will turn ON after the<br />

set delay time has elapsed. The setting range is 0 to 9,999. The default is<br />

0 (disabled).<br />

8. Setting OFF Delay Times<br />

When an input with an OFF delay turns OFF, the output will turn OFF after<br />

the set delay time has elapsed. The setting range is 0 to 9,999. The default<br />

is 0 (disabled).<br />

9. Switching ON/OFF Delay Time Unit<br />

Select either seconds or minutes for the ON/OFF delay time unit. The default<br />

is seconds.<br />

10. Selecting the Number of Banks to Use<br />

Select a number from 0 to 3 for the Bank Numbers Used parameter.<br />

(For models with two event inputs, select a number between 0 and 2.)<br />

Note If a work bit is assigned for either the Event Input Data 1 or Event<br />

Input Data 2 parameter for a model that does not support event inputs<br />

1 and 2 and if a number greater than 0 is set for the Bank Numbers<br />

Used parameter, then event inputs 1 and 2 will be used for<br />

bank selection.<br />

For example, if the Bank Numbers Used parameter is set to 2 for a model<br />

with event inputs 3 and 4, and the following settings are made, then event<br />

input 1 (work bit 1) and event input 2 (work bit 2) will be used for bank selection.<br />

Event Input Data 1: Work bit 1<br />

Event Input Data 2: Work bit 2<br />

Event Input Data 3: Event input 3 (external input)<br />

Event Input Data 4: Event input 4 (external input)<br />

To use event input 3 (external input) and event input 4 (external input) for<br />

bank selection, make the following settings:<br />

Event Input Data 1: Event input 3 (external input)<br />

Event Input Data 2: Event input 4 (external input)<br />

Event Input Data 3: Work bit 1<br />

Event Input Data 4: Work bit 2