05.03.2013 Views

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Calibrating Analog Input (Analog Input) Section 6-5<br />

a--1<br />

4677<br />

str no<br />

6-5-2 Calibrating a Voltage Input<br />

adj 30<br />

Input type 27 or 28:<br />

1v-5<br />

c7c3<br />

Input type 29:<br />

2v10<br />

b104<br />

6. When the M Key is pressed, the status changes as shown to the left.<br />

Set the STV to 1 mA.<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

7. When the M Key is pressed, the status changes as shown to the left.<br />

The data to be temporarily registered is not displayed if it is not complete.<br />

Press the U Key. The No. 2 display changes to yes. Release the key and<br />

wait two seconds or press the M Key. This stores the temporarily registered<br />

calibration data to EEPROM.<br />

To cancel the saving of temporarily registered calibration data to EE-<br />

PROM, press the M Key (while no is displayed in the No. 2 display) without<br />

pressing the U Key.<br />

8. The calibration mode is ended by turning the power OFF.<br />

For <strong>Controllers</strong> that have a transfer output (<strong>E5AN</strong>/EN-H@@F), transfer<br />

output calibration continues to be performed. For details on the settings,<br />

refer to 6-6 Calibrating the Transfer Output on page 292.<br />

In this example, calibration is shown for a Controller with a voltage input set as<br />

the input type.<br />

1,2,3... 1. Connect the power supply.<br />

2. Connect an STV and DMM to the voltage input terminals, as shown in the<br />

following diagram.<br />

E5CN-H<br />

<strong>E5AN</strong>/EN-H<br />

STV<br />

DMM<br />

9<br />

Input power supply<br />

10<br />

4<br />

5<br />

−<br />

+<br />

STV<br />

DMM<br />

Input power supply<br />

3. Turn the power ON.<br />

4. Move to the calibration level.<br />

This starts the 30-minute aging timer. This timer provides an approximate<br />

timer for aging. After 30 minutes have elapsed, the No. 2 display changes<br />

to 0. You can advance to the next step in this procedure even if 0 is not<br />

displayed.<br />

5. When the M Key is pressed, the status changes as shown to the left.<br />

The No. 2 display at this time shows the currently entered count value in<br />

hexadecimal. Set the STV as follows:<br />

Input type 27 or 28: 5 V<br />

Input type 29: 10 V<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

1<br />

2<br />

19<br />

17<br />

−<br />

+<br />

291

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!