310<br />

Meaning Countermeasures<br />

The communications line became unstable<br />

when Controller power was turned ON or<br />

interrupted, and the host device read the<br />

unstable status as data.<br />

The communications data was corrupted<br />

from noise from the environment.<br />

Appendix<br />

Initialize the reception buffer in the host device before sending the first<br />

command and after turning OFF the power to the Controller.<br />

Try using a slower baud rate.<br />

Separate the communications cable from the source of noise.<br />

Use a shielded, twisted-pair cable for the communications cable.<br />

Use as short a communications cable as possible, and do not lay or loop<br />

extra cable.<br />

To prevent inductive noise, do not run the communications cable parallel<br />

to a power line.<br />

If noise countermeasures are difficult to implement, use an Optical Interface.<br />

Note For details on errors, refer to E5CN-H/<strong>E5AN</strong>-H/<strong>E5EN</strong>-H <strong>Digital</strong> <strong>Controllers</strong> Communications <strong>Manual</strong><br />

Advanced Type (Cat. No. H159).