Wiring Terminals Section 2-2<br />

CT Inputs When the HB alarm, HS alarm, or heater overcurrent alarm is to be used<br />

with the E5CN-H@M@-500 with an E53-CN@H/HH@N2 Option Unit, connect<br />

a current transformer (CT) across terminals 14 and 15 or terminals<br />

13 and 15 (no polarity).<br />

When the HB alarm, HS alarm, or heater overcurrent alarm is to be used<br />

with the <strong>E5AN</strong>/EN-H@@H@-500 or <strong>E5AN</strong>/EN-H@@HH@-500, connect a<br />

current transformer (CT) across terminals 14 and 15 or terminals 15 and<br />

16 (no polarity).<br />

14<br />

15<br />

CT<br />

E53-CN@H@N2<br />

(for E5CN-H)<br />

13<br />

14<br />

15<br />

CT1<br />

E53-CN@HH@N2<br />

Transfer Output On the E5CN-H@M@-500 with an E53-CN@FN2, the transfer output is<br />

output across terminals 14 and 15.<br />

On the <strong>E5AN</strong>/EN-H@@F-500, transfer output is output across terminals<br />

27 and 28.<br />

+v<br />

+v<br />

+<br />

+<br />

14<br />

27<br />

L<br />

L<br />

15<br />

28<br />

−<br />

−<br />

Current<br />

Current<br />

Even with models that do not have a transfer output, control outputs 1 or 2 can<br />

be used as a simple transfer output if it is a current output or linear output. For<br />

details on the operation, refer to 4-14 Using the Transfer Output.<br />

Remote SP Input The <strong>E5AN</strong>-H and <strong>E5EN</strong>-H support remote SP inputs. To use remote SP,<br />

connect to terminals 29 and 30.<br />

CT2<br />

Remote SP inputs are not electrically isolated from the internal circuits. When<br />

using a grounding thermocouple, do not connect any of the remote SP input<br />

terminals to the ground. (If a remote SP input terminal is connected to the<br />

ground, errors will occur in the measured temperature as a result of leakage<br />

current.)<br />

14<br />

15<br />

CT<br />

CT1<br />

CT2<br />

<strong>E5AN</strong>/EN-H@@H@-500 <strong>E5AN</strong>/EN-H@@HH@-500<br />

Output type Specifications<br />

Current 4 to 20 mA DC, Load: 600 Ω max., Resolution: 10,000<br />

29<br />

30<br />

E53-CN@FN2<br />

(for E5CN-H)<br />

+<br />

4 to 20 mA<br />

−<br />

<strong>E5AN</strong>/EN-H<br />

<strong>E5AN</strong>/EN-H@@F-500<br />

14<br />

15<br />

16<br />

37