Alarm Outputs Section 3-9<br />

3-9-2 Alarm Values<br />

∗.a1l<br />

∗.a2l<br />

∗.a3l<br />

∗.a1h<br />

∗.a2h<br />

∗.a3h<br />

∗.a-1<br />

∗.a-2<br />

∗.a-3<br />

Bank* Alarm Value<br />

Lower Limit<br />

(∗: 0 to 7)<br />

Alarm Value Upper<br />

Limit Value<br />

(∗ : 0 to 7)<br />

Alarm Value<br />

(∗: 0 to 7)<br />

Alarm values are indicated by “X” in the table on the previous page. When<br />

the upper and lower limits are set independently, “H” is displayed for<br />

upper limit values, and “L” is displayed for lower limit values.<br />

To set the alarm upper and lower limits for deviation, set the upper and<br />

lower limits in the Alarm 1 to 3 Upper Limit and Alarm 1 to 3 Lower Limit<br />

parameters.<br />

Alarm values can be set for each bank. Select the bank number in the<br />

Display Bank Selection parameter in the bank setting level, and set the<br />

Alarm Value, Alarm Value Upper Limit (1 to 3), and Alarm Value Lower<br />

Limit (1 to 3) parameters for that bank.<br />

When the Alarm Value, Alarm Value Upper Limit, and Alarm Value Lower<br />

Limit parameters in the operation level are changed, the changes will be<br />

reflected in those parameters for the current bank.<br />

Operating Procedure This procedure sets alarm 1 for bank number 1 as an upper-limit alarm. The<br />

related parameters and settings are shown below. The alarm is output when<br />

the set point exceeds 10°C. (In this example, the temperature unit is °C.)<br />

Alarm 1 type = 2 (Upper-limit alarm)<br />

Bank 1 Alarm value 1 = 10<br />

Initial Setting Level 1. Press the O Key for at least three seconds to move from the operation<br />

Input Type<br />

level to the initial setting level.<br />

C<br />

in-t 5<br />

alt1 2<br />

25.0<br />

100.0<br />

Alarm 1 Type<br />

2. Select the Alarm 1 Type parameter by pressing the M Key. Confirm that<br />

the set value is 2. The default value is 2 (Upper-limit alarm).<br />

3. To return to the operation level, press the O Key for at least one second.<br />

Bank Setting Level 4. Press the O Key to move to the bank setting level.<br />

d.bnk 0<br />

d.bnk 1<br />

PV/SP<br />

Display Bank<br />

Selection<br />

5. Use the U and D Keys to set 1.<br />

69