Alarm Delays Section 4-11<br />

4-11 Alarm Delays<br />

4-11-1 Alarm Delays<br />

112<br />

Delays can be set for the alarm outputs. ON and OFF delays can be set<br />

separately for alarms 1, 2, and 3. The ON and OFF delays for alarm 1<br />

function only for the alarm function. If the alarm 1 function is set to be output<br />

as an OR with other alarms (i.e., the heater burnout alarm, HS alarm,<br />

heater overcurrent alarm, or input error output alarm), delays cannot be<br />

set for the other alarms. The ON and OFF delays for alarms 1, 2, and 3<br />

also apply to the individual SUB1, SUB2, and SUB3 indicators and to<br />

communications status. The alarm ON delays will also function when<br />

power is turned ON or when moving from the initial setting level to operation<br />

level (e.g., to software resets). All outputs will turn OFF and the OFF<br />

delays will not function when moving to the initial setting level or when an<br />

alarm is output for a A/D converter error.<br />

Operation of Alarm ON and OFF Delays (for an Upper-limit Alarm)<br />

Parameters Related to Alarm Delays<br />

PV<br />

Alarm setting<br />

Alarm status<br />

ON delay<br />

set time<br />

ON delay set time<br />

OFF delay<br />

set time<br />

Alarm Latch = OFF<br />

Alarm hysteresis<br />

Alarm will not turn ON.<br />

The alarm will not turn ON if the time that the alarm is ON is equal to or<br />

less than the ON delay set time. Also, the alarm will not turn OFF if the<br />

time that the alarm is OFF is equal to or less than the OFF delay set time.<br />

If an alarm turns OFF and then back ON during the ON delay time, the<br />

time will be remeasured from the last time the alarm turns ON. Also, if an<br />

alarm turns ON and then back OFF during the OFF delay time, the time<br />

will be remeasured from the last time the alarm turns OFF.<br />

Parameter name Symbol Set (monitor) values<br />

Alarm 1 ON Delay a1on 0 to 999 (s)<br />

Alarm 2 ON Delay a2on 0 to 999 (s)<br />

Alarm 3 ON Delay a3on 0 to 999 (s)<br />

Alarm 1 OFF Delay a1of 0 to 999 (s)<br />

Alarm 2 OFF Delay a2of 0 to 999 (s)<br />

Alarm 3 OFF Delay a3of 0 to 999 (s)