Advanced Function Setting Level Section 5-10<br />

See<br />

rt RT<br />

Function<br />

Setting<br />

See<br />

hsu HS Alarm Use<br />

Function<br />

Setting<br />

■ Related Parameters<br />

Auto/manual switch (operation level): Page 178<br />

This parameter executes robust tuning (RT).<br />

When AT or ST is executed with RT selected, PID constants are automatically<br />

set which make it hard for control performance to degenerate even<br />

when control object characteristics are changed.<br />

Even when hunting occurs for PID constants when AT or ST is executed<br />

in normal mode, it is less likely to occur when AT or ST is executed in RT<br />

mode.<br />

■ Related Parameters<br />

AT execute/cancel (PID setting level): Page 192<br />

PID * proportional band (PID setting level): Page 217<br />

PID * integral time (PID setting level): Page 217<br />

PID * derivative time (PID setting level): Page 217<br />

PID ON/OFF (initial setting level): Page 228<br />

ST (initial setting level): Page 228<br />

Set this parameter to use HS alarms.<br />

The control must be set to 2-PID<br />

control.<br />

The input type must be set to temperature<br />

input.<br />

Setting range Default<br />

on: RT function OFF, off: RT function ON off<br />

Setting range Default<br />

on: Enabled, off: Disabled on<br />

Heater burnout, HS alarms, and<br />

heater overcurrent detection must be<br />

supported.<br />

Alarm 1 must be assigned.<br />

257