Communications Function Section 1-4<br />

Setting Communications<br />

Data<br />

2. Press the O Key for less than one second to move from the initial setting<br />

level to the communications setting level.<br />

3. Select the parameters as shown below by pressing the M Key.<br />

4. Press the U or D Key to change the parameter setting.<br />

psel Protocol Setting<br />

cwf<br />

M<br />

u-no Communications Unit No.<br />

1<br />

M<br />

Communications Baud Rate<br />

bps<br />

9.6<br />

M<br />

len Communications Data Length<br />

7 (See note.)<br />

M<br />

sbit Communications Stop Bits<br />

2 (See note.)<br />

M<br />

prty Communications Parity<br />

even<br />

M<br />

Send Data Wait Time<br />

sdwt<br />

20<br />

M<br />

Note The Protocol Setting parameter is displayed only when CompoWay/F communications<br />

are being used.<br />

Match the communications specifications of the E5CN/AN/EN-H and the host<br />

computer. If a 1:N connection is being used, ensure that the communications<br />

specifications for all devices in the system (except the communications Unit<br />

No.) are the same.<br />

Parameter name Symbol Setting (monitor) value Selection symbols Default Unit<br />

Protocol Setting psel CompoWay/F (SYSWAY), cwf, mod CompoWay/F None<br />

Modbus<br />

(SYSWAY)<br />

Communications<br />

Unit No.<br />

u-no 0 to 99 1 None<br />

Communications bps 1.2, 2.4, 4.8, 9.6, 19.2, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4. 9.6 kbps<br />

Baud Rate<br />

38.4, 57.6<br />

57.6<br />

Communications<br />

Data Length<br />

len 7, 8 7 Bits<br />

Communications<br />

Stop Bits<br />

sbit 1, 2 2 Bits<br />

Communications<br />

Parity<br />

prty None, Even, Odd none, even, odd Even None<br />

Send Data Wait<br />

Time<br />

sdwe 0 to 99 20 ms<br />