Setting Output Specifications Section 3-5<br />

3-5 Setting Output Specifications<br />

3-5-1 Control Periods<br />

52<br />

cp<br />

c-cp<br />

Control Period<br />

(Heating)<br />

Control Period<br />

(Cooling)<br />

The following table shows the parameters related to outputs. Each of the<br />

parameters is described in detail following the table.<br />

(●: Supported)<br />

3-5-2 Direct and Reverse Operation<br />

Parameter Standard<br />

models<br />

Positionproportional<br />

models<br />

cp Control Period (Heating) ●<br />

c-cp Control Period (Cooling) ●<br />

orev Direct/Reverse Operation ● ●<br />

out1 Control Output 1 Assignment ●<br />

out2 Control Output 2 Assignment ●<br />

sub1 Auxiliary Output 1 Assignment ● ●<br />

sub2 Auxiliary Output 2 Assignment ● ●<br />

sub3 Auxiliary Output 3 Assignment ●<br />

Set the output periods (control periods). Though a shorter period provides<br />

better control performance, it is recommended that the control period be<br />

set to 20 seconds or longer for a relay output to preserve the service life<br />

of the relay. After the settings have been made in the initial setup, readjust<br />

the control period, as required, by means such as trial operation.<br />

Set the control periods in the Control Period (Heating) and Control Period<br />

(Cooling) parameters in the initial setting level. The default is 20 seconds.<br />

The Control Period (Cooling) parameter is used only for heating/cooling<br />

control.<br />

When the control output is used as a current output or linear voltage output,<br />

the Control Period settings cannot be used.<br />

The control period can be set for standard models only.<br />

Direct operation increases the manipulated variable whenever the process<br />

value increases. Reverse operation decreases the manipulated variable<br />

whenever the process value increases.<br />

Manipulated variable Manipulated variable<br />

100%<br />

100%<br />

0%<br />

Low Set Value High<br />

temperature<br />

temperature<br />

0%<br />

Low Set Value High<br />

temperature<br />

temperature<br />

Direct operation Reverse operation