SV-iS7 User Manual - Inverter Drive Supermarket
SV-iS7 User Manual - Inverter Drive Supermarket
SV-iS7 User Manual - Inverter Drive Supermarket
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
4) Shift from Remote to Local<br />
Chapter 7 Basic Functions<br />
In case of Shift from Remote to Local, the signal representing the command source and frequency source at the top of<br />
MON Mode turns to K/K. The inverter stops if it has been operating in Remote status.<br />
5) Shift from Local to Remote<br />
In case of shift from Local to Remote, K/K at the top of MON Mode is represented by a different signal in conformity to<br />
the previously set command source and frequency source.<br />
Shift to Remote is available during Local operation but the movements might vary according to which source it is set at.<br />
(1) When the Terminal Block is Command Source<br />
Shift from Local to Remote during operation leads to operation by the command of the terminal block. That is, if RX<br />
is in the terminal block and the motor is rotating forward in Local, shift to Remote makes the motor rotate in the<br />
reverse direction.<br />
(2) Digital Command Source<br />
Digital command source refers to all the command sources except for the terminal block source, that is,<br />
communication, PLC and keypad. In case of digital command source, the inverter stops and then starts when the<br />
next command is given. The target frequency is set at the currently set frequency source.<br />
6) Terminal in with Power on<br />
When ADV-10 Power On Run is No, if the terminals of FX, RX, FWD_JOG, REV_JOG, PRE EXCITE are in, shift to<br />
Local still enables the keypad to operate the inverter. However, re-shift to Remote disables operation. That is, one of the<br />
5 aforementioned terminals is ON with power on, the motor does not work whether FX or RX. Therefore, with Power<br />
On Run being No, terminal Run is available after the inverter is turned on and all the terminals off.<br />
7) When Motor Stops Due to Trip during Operation<br />
If the motor stops due to a trip during operation and is reset, in Local Mode, the inverter motor is operated by the keypad,<br />
but in Remote Mode again, it does not operate no matter how many operating commands are given to the terminal<br />
block. That is, the motor starts rotating after all the operating terminals is turned OFF and the operating command<br />
terminal is turned ON.<br />
7.1.7 Prevention of forward or reverse rotation: Run Prevent<br />
Group Code No. Function Display Setting Display Setting Range Unit<br />
ADV 09 Run Prevent 0 None 0~2 -<br />
You can select a motor rotation direction to prevent.<br />
None : Both forward and reverse are available.<br />
Forward Prev : Forward operation is prevented.<br />
Reverse Prev : Reverse operation is prevented.<br />
7-14