4) Shift from Remote to Local<br />

Chapter 7 Basic Functions<br />

In case of Shift from Remote to Local, the signal representing the command source and frequency source at the top of<br />

MON Mode turns to K/K. The inverter stops if it has been operating in Remote status.<br />

5) Shift from Local to Remote<br />

In case of shift from Local to Remote, K/K at the top of MON Mode is represented by a different signal in conformity to<br />

the previously set command source and frequency source.<br />

Shift to Remote is available during Local operation but the movements might vary according to which source it is set at.<br />

(1) When the Terminal Block is Command Source<br />

Shift from Local to Remote during operation leads to operation by the command of the terminal block. That is, if RX<br />

is in the terminal block and the motor is rotating forward in Local, shift to Remote makes the motor rotate in the<br />

reverse direction.<br />

(2) Digital Command Source<br />

Digital command source refers to all the command sources except for the terminal block source, that is,<br />

communication, PLC and keypad. In case of digital command source, the inverter stops and then starts when the<br />

next command is given. The target frequency is set at the currently set frequency source.<br />

6) Terminal in with Power on<br />

When ADV-10 Power On Run is No, if the terminals of FX, RX, FWD_JOG, REV_JOG, PRE EXCITE are in, shift to<br />

Local still enables the keypad to operate the inverter. However, re-shift to Remote disables operation. That is, one of the<br />

5 aforementioned terminals is ON with power on, the motor does not work whether FX or RX. Therefore, with Power<br />

On Run being No, terminal Run is available after the inverter is turned on and all the terminals off.<br />

7) When Motor Stops Due to Trip during Operation<br />

If the motor stops due to a trip during operation and is reset, in Local Mode, the inverter motor is operated by the keypad,<br />

but in Remote Mode again, it does not operate no matter how many operating commands are given to the terminal<br />

block. That is, the motor starts rotating after all the operating terminals is turned OFF and the operating command<br />

terminal is turned ON.<br />

7.1.7 Prevention of forward or reverse rotation: Run Prevent<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

ADV 09 Run Prevent 0 None 0~2 -<br />

You can select a motor rotation direction to prevent.<br />

None : Both forward and reverse are available.<br />

Forward Prev : Forward operation is prevented.<br />

Reverse Prev : Reverse operation is prevented.<br />