Chapter 8 Applied Functions<br />

8.1.8 PID control<br />

1) PID Basic Operation<br />

This is a method commonly used among the ones of auto control. PID means P: Proportional, I: Integral, and D:<br />

Differential. By combining these 3, better control is available.<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

APP<br />

IN<br />

8-12<br />

01 App Mode 2 Proc PID 0~4 -<br />

16 PID Output - - - -<br />

17 PID Ref Value - - - -<br />

18 PID Fdb Value - - - -<br />

19 PID Ref Set - 50.00 -100~100 %<br />

20 PID Ref Source 0 Keypad-1 0~10 -<br />

21 PID F/B Source 0 V1 0~10 -<br />

22 PID P-Gain - 50.0 0~1000 %<br />

23 PID I-Time - 10.0 0~32.0 Sec<br />

24 PID D-Time - 0 0~1000 MSec<br />

25 PID F-Gain - 0.0 0~1000 %<br />

26 P Gain Scale - 100.0 0~100 %<br />

27 PID Out LPF - 0 M0~10000 msec<br />

29 PID Limit Hi - 60.00 0~300 Hz<br />

30 PID Limit Lo - 0.00 0~300 Hz<br />

31 PID Out Inv - No 0~1 -<br />

32 PID Out Scale - 100.0 0.1~1000 %<br />

34 Pre-PID Freq - 0.00 0~Max. Freq Hz<br />

35 Pre-PID Exit - 0.0 0~100 %<br />

36 Pre-PID Delay - 600 0~9999 Sec<br />

37 PID Sleep DT - 60.0 0~999.9 Sec<br />

38 PID Sleep Freq - 0.00 0~Max. Freq. Hz<br />

39 PID WakeUp Lev - 35 0~100 %<br />

40 PID WakeUp Mod 0 Below Level 0~2 -<br />

42 PID Unit Sel 0 Hz 0~12 -<br />

43 PID Unit Gain - 100.0 0~650 %<br />

44 PID Unit Scale 2 X 1 0~2 -<br />

45 PID P2-Gain - 100.0 0~1000 %<br />

65~75 Px Define 22 I-Term Clear 0~48 -<br />

65~75 Px Define 23 PID Openloop 0~48 -<br />

65~75 Px Define 24 P Gain2 0~48 -