Chapter 8 Applied Functions<br />

8.1.38 Multi-function output On/Off control<br />

8-56<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

66 OnOff Ctrl Src 1 V1 - -<br />

ADV 67 On-C Level - 90.00 10~100% %<br />

68 Off-C Level - 10.00<br />

0~Output contact on<br />

level<br />

%<br />

OUT 31~33 Relay x or Q1 34 On/Off Control - -<br />

If the analog input value is over the set value, the output relay or multi-function output terminal can be turned ON or<br />

OFF.<br />

Select the analog input to use for ON/OFF control at ADV-66 and set the levels at which the output terminal is ON<br />

and OFF at ADV-67 and 68 respectively. If the analog input value is over the value set at ADV-67, the output<br />

terminal is ON and if below ADV-68, it is OFF.<br />

8.1.39 MMC function<br />

This is used when multiple motors are controlled by one inverter in the fan or pump system. The motor connected to<br />

the inverter output(main motor) controls speed by PID control and other motors(auxiliary motors), connected to the<br />

common power source by the relay inside the inverter, conduct On/Off control.<br />

For the relay for control of the auxiliary motors, the Relay 1 and 2 of the standard I/O card of the inverter and multi-<br />

function output terminal Q1 are used. If the extended I/O option card is connected to the inverter option slot, up to 3<br />

relay outputs are available.<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

APP 01 App Mode 3 MMC - -<br />

20 Aux Motor Run - 0 0~4 -<br />

21 Starting Aux - 1 1~4 -<br />

22 Auto Op Time - 0:00 xx:xx Min<br />

23 Start Freq 1 - 49.99 0~60 Hz<br />

24 Start Freq 2 - 49.99 0~60 Hz<br />

25 Start Freq 3 - 49.99 0~60 Hz<br />

APO<br />

26 Start Freq 4 - 49.99 0~60 Hz<br />

27 Stop Freq 1 - 15.00 0~60 Hz<br />

28 Stop Freq 1 - 15.00 0~60 Hz<br />

29 Stop Freq 1 - 15.00 0~60 Hz<br />

30 Stop Freq 1 - 15.00 0~60 Hz<br />

31 Aux Start DT - 60.0 0~3600.0 Sec<br />

32 Aux Stop DT - 60.0 0~3600.0 Sec