Chapter 8 Applied Functions<br />

4) PID Sleep Mode(Sleep)<br />

APP-37 PID Sleep DT, APP-38 PID Sleep Freq : If the inverter continues to operate for the time set in APP-37 PID Sleep<br />

DT under the frequency set in APP-38 Sleep Freq, is stops operating and goes into Sleep Mode. For the threshold of shift<br />

from PID Sleep Mode to PID operation mode back, see APP-39 PID WakeUp Lev.<br />

APP-39 PID WakeUp Lev, APP-40 PID WakeUp Mod : Sets the threshold of starting PID operation from the PID sleep<br />

mode described above. If you select 0(Below Level) in APP-40 and the feedback is smaller than set in APP-39 PID<br />

WakeUp Lev, PID operation resumes. No. 1(Above Level) restarts operation when it is larger than the value set in APP-39.<br />

No. 2(Beyond Level) restarts operation when the difference between the reference and feedback is larger than the value<br />

set in APP-39.<br />

5) PID Operation by pass (PID Openloop)<br />

If, among multi-function terminal blocks, the terminal set at No. 22 PID Openloop in IN-65~75 Px Define is input, PID<br />

operation stops and changes to normal operation. The terminal OFF, PID operation resumes.<br />

8-16<br />

PID<br />

Feedback<br />

Output<br />

frequenc<br />

y<br />

Fx<br />

PID<br />

operation<br />

section<br />

PID Sleep Freq(APP-<br />

38)<br />

PID Sleep DT(APP-<br />

37)<br />

Sleep<br />

section<br />

WakeUp<br />

section<br />

PID WakeUp Lev<br />

(APP-39)