Chapter 10 Protective Functions<br />

10-3<br />

PRT-21 OL Trip Level, PRT-22 OL Trip Time : The inverter output is blocked or stops decelerating according to the<br />

method set in PRT-17 if the current flowing in the motor is higher than the value set at OL Trip Level and the current<br />

continues to flow for the OL Trip Time.<br />

PRT-17 OL Warn Select : Warning signal is released using the multi-function output terminal of the terminal block or<br />

relay when a load of OL warning level is supplied. It gets active if 1 Yes is selected and not active if 0 No is selected.<br />

PRT-18 OL Warn Level, PRT-19 OL Warn Time : The multi-function output(Relay 1, Relay2, Q1) releases the<br />

warning signal if the current flowing in the motor is higher than the OL Warn Level and the current continues to flow for<br />

the OL Warn Time. The multi-function output terminal and relay release signals if Over Load is selected at OUT-31~33.<br />

The output of the inverter is not blocked.<br />

10.1.3 Stall prevention<br />

In case of a stall due to overload, over current flows in the motor possibly causing overhead or damage to the motor of<br />

interrupting the system process of the motor load side. The output frequency of the inverter is automatically controlled in<br />

order to prevent the motor stall due to overload.<br />

Group Code No. Function Display Initial Setting Display Setting Range Unit<br />

PRT<br />

Current<br />

Multi-Function Output<br />

t : PRT-19<br />

t t<br />

PRT-18<br />

50 Stall Prevent - 111 - Bit<br />

51 Stall Freq 1 - 60.00 Starting Freq ~ Stall Freq 1 Hz<br />

52 Stall Level 1 - 180 30~250 %<br />

53 Stall Freq 2 - 60.00 Stall Freq 1~ Stall Freq 3 Hz<br />

54 Stall Level 2 - 180 30~250 %<br />

55 Stall Freq 3 - 60.00 Stall Freq 2~ Stall Freq 4 Hz<br />

56 Stall Level 3 - 180 30~250 %<br />

57 Stall Freq 4 - 60.00 Stall Freq 3~ Max. Freq Hz<br />

58 Stall Level 4 - 180 30~250 %<br />

OUT 31~33 Relay1,2, Q1 9 Stall - -