Applied Function Group (PAR � APP)<br />

No.<br />

Commu<br />

nication<br />

No.<br />

Function<br />

Display<br />

21 0h1815 PID<br />

F/B Source<br />

Name Setting Range<br />

PID Feedback selection<br />

0 V1<br />

1 I1<br />

2 V2<br />

3 I2<br />

4 Int 485<br />

5 Encoder<br />

6 FieldBus<br />

7 PLC<br />

8 Synchro<br />

9 Binary Type<br />

Initial<br />

Value<br />

Chapter 13 Table of Functions<br />

Shift<br />

in<br />

Oper<br />

ation<br />

Page V<br />

/<br />

F<br />

Control Mode<br />

S<br />

L<br />

V<br />

C<br />

S<br />

L<br />

T<br />

0:V1 X 8-12 O O O X X<br />

22 0h1816 PID P-Gain PID proportional gain 0~1000[%] 50.0 O 8-12 O O O X X<br />

23 0h1817 PID I-Time PID integral calculus time 0~200.0[sec] 10.0 O 8-12 O O O X X<br />

24 0h1818 PID D-Time PID differential time 0~1000[msec] 0 O 8-12 O O O X X<br />

25 0h1819 PID F-Gain PID Feed forward gain 0~1000.0[%] 0.0 O 8-12 O O O X X<br />

26 0h181A P Gain Scale Proportional gain scale 0~100.0[%] 100.0 X 8-12 O O O X X<br />

27 0h181B PID Out LPF PID output filter 0~10000[ms]<br />

PID lower limit<br />

0 O 8-12 O O O X X<br />

29 0h181D PID Limit Hi PID upper limit frequency frequency[Hz]<br />

~300[Hz]<br />

60.00 O 8-12 O O O X X<br />

30 0h181E PID Limit Lo PID lower limit frequency<br />

-300 ~ PID upper<br />

limit frequency[Hz]<br />

-60 O 8-12 O O O X X<br />

31 0h181F PID Out Inv PID output reversal<br />

0<br />

1<br />

No<br />

Yes<br />

0:No X 8-12 O O O X X<br />

32 0h1820 PID Out Scale PID output scale 0.1~1000[%] 100.0 X 8-12 O O O X X<br />

34 0h1822 Pre-PID Freq<br />

PID control period<br />

movement frequency<br />

0~maximum<br />

frequency[Hz] 0.00 X 8-12 O O O X X<br />

35 0h1823 Pre-PID Exit<br />

PID control period<br />

movement level<br />

0~100[%] 0.0 X 8-12 O O O X X<br />

36 0h1824 Pre-PID Delay<br />

PID control period<br />

movement delay time<br />

0~9999[sec] 600 O 8-12 O O O X X<br />

37 0h1825 PID Sleep DT<br />

PID sleep mode delay<br />

time<br />

0~999.9[sec] 60.0 O 8-12 O O O X X<br />

38<br />

PID Sleep<br />

0h1826<br />

Freq<br />

PID Sleep mode<br />

frequency<br />

0~maximum<br />

frequency[Hz] 0.00 O 8-12 O O O X X<br />

39<br />

PID WakeUp<br />

0h1827<br />

Lev<br />

PID Wake up level 0~100[%] 35 O 8-12 O O O X X<br />

40<br />

PID WakeUp<br />

0h1828<br />

Mod<br />

PID Wake up mode<br />

setting<br />

0<br />

1<br />

2<br />

Below Level<br />

Above Level<br />

Beyond Level<br />

0:Below<br />

Level<br />

O 8-12 O O O X X<br />

42 0h182A PID Unit Sel PID control period unit 0 %<br />

0:% O 8-12 O O O X X<br />

selection<br />

1 Bar<br />

2 mBar<br />

3 Pa<br />

4 KPa<br />

5 Hz<br />

6 rpm<br />

7 V<br />

8 I<br />

9 kW<br />

V<br />

C<br />

T<br />

13-28