Chapter 8 Applied Functions<br />

OUT-30 Realy 1 ~ OUT-32 MO1 Define : Sets the multi-function relay or multi-function output at No. 16 <strong>Inverter</strong><br />

Line and No. 17 Comm Line. For relay motion sequence, see the figure below.<br />

Output<br />

frequency<br />

Operation<br />

command<br />

PX<br />

(Exchange)<br />

PX<br />

(Comm Line)<br />

PX<br />

(<strong>Inverter</strong> Line)<br />

8.1.24 Cooling fan control<br />

<strong>Inverter</strong><br />

operation<br />

t : 500 msec<br />

Group Code No. Function Display Initial Setting Display default Unit<br />

ADV 64 FAN Control<br />

t t<br />

Common<br />

operation<br />

Speed frequency interval<br />

<strong>Inverter</strong><br />

operation<br />

0 During Run<br />

1 Always On<br />

2 Temp Control<br />

0:<br />

During<br />

Run<br />

This if the function of On/Off control of the fan attached for cooling the heat-sink of the inverter. This is used for<br />

frequently starting/stopping loads or for a quiet environment without the noise of the cooling fan when stopping. This<br />

also helps lengthen the life of the cooling fan.<br />

No. 0 During Run (active during operation only) : If an operating command is input with the power ON in the<br />

inverter, the cooling fan starts operating. If the operating command is OFF and the inverter output is blocked, the<br />

cooling fan stops. If the temperature of the inverter heat sink is higher than a certain degree, the cooling fan operates<br />

regardless of the operating command.<br />

No. 1 Always ON (always active) : The cooling fan is always active when power is supplied to the inverter.<br />

No. 2 Temp Control (temperature check) : The cooling fan is not active even when power is supplied to the<br />

inverter and an operating command is input. However, if the temperature of the inverter heat sink is higher than a<br />

certain degree, cooling fan is active.<br />

Caution<br />

Though 11~75kW class sets ADV-64 as “During Run”, FAN could be active as In case of operation<br />

above regular temperature of cooling fan by current input harmonics or noises.<br />

-<br />

8-43