14.11.2012 Views

SV-iS7 User Manual - Inverter Drive Supermarket

SV-iS7 User Manual - Inverter Drive Supermarket

SV-iS7 User Manual - Inverter Drive Supermarket

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chapter 8 Applied Functions<br />

ADV-61 SS Sup-Current : Controls the current during speed search motion on the basis of the motor rated current. The<br />

gain of the controller is set at ADV-62 and 63.<br />

ADV-64 SS Block Time : Blocks output for the set period of time and then starts operation before starting speed search.<br />

Speed search operation is mostly used for loads with high inertia. In case of a load with high friction, it is recommended to<br />

restart after stop.<br />

The <strong>iS7</strong> series is designed to conduct normal operation in case of an instantaneous interruption shorter than 15mSec<br />

when being used within the rated output. The inverter with 200V input voltage and the inverter with 400V input voltage<br />

guarantee the instantaneous interruption time when the input voltage supplied to the inverter is 200~230Vac and<br />

380~460Vac respectively. The current is on the basis of the static torque load current(CT load).<br />

The DC voltage inside the inverter might vary according to the output load. Therefore if the instantaneous interruption time<br />

is longer than 15mSec or the output is higher than the rated output, a low voltage trip(Low Voltage) might occur.<br />

8.1.20 Automatic Restart<br />

1) Automatic Restart<br />

8-38<br />

Group Code No. Function Display Setting Range Initial Value Unit<br />

PRT<br />

08 RST Restart 0:n /Yes (1) 0: No/Yes(1) -<br />

09 Retry Number 0 ~ 10 0~10 -<br />

10 Retry Delay 0 ~ 60.0 1.0 Sec<br />

CON 71~75 SS-Related Function - - -<br />

This is used to prevent a system interruption with the inverter protective function in case of noise and so on.<br />

PRT-08 RST Restart, PRT-09 Retry Number, PRT-10 Retry Delay : It operates when PRT-08 RST Restart set to<br />

YES and The available number of automatic restart is set at PRT-09. In case of a trip during operation, the inverter<br />

conducts automatic restart after the time set in PRT-10 Retry Delay. At each automatic restart, the number of<br />

automatic restarts decreases by 1 inside the inverter and a set number of trips occur and if the number is 0,<br />

automatic restart is not carried out even if a trip occurs.<br />

If a trip does not occur within 60 seconds after automatic restart, the number of automatic restarts that was reduced<br />

inside the inverter increases again. The maximum increase number is limited to the number of restarts.<br />

Automatic restart is not carried out in case of a stop caused by low voltage, emergency stop (Bx), overheat or<br />

hardware problem (HW Diag).<br />

The acceleration of automatic restart is the same as speed search operation. Thus the functions of CON72~75 can<br />

be set according to the load and for the speed search function, see Page 8-36.<br />

Caution<br />

In case of operation with the number of automatic restarts set, the reset is terminated and the motor<br />

is rotated automatically by the inverter.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!