Chapter 8 Applied Functions<br />

CON-48 ACR P-Gain, CON-49 ACR I Gain : Used in sensorless speed/torque and vector speed/torque modes and<br />

adjusts the P gain and I gain of the current PI controller.<br />

IN-65~75 Px Define<br />

36 : ASR Gain2<br />

If the set terminal is input, the gain can be changed after the change time(CON-19).<br />

37 : ASR P/PI<br />

Moves during stop. If the set terminal is input, the integral controller is not active.<br />

6) Torque Limit<br />

The size of the torque reference is adjusted by limiting the speed controller output. As in the following figure, both reverse<br />

and regenerative limits for forward and reverse operation can be set.<br />

CON-53 Torque Lmt Src : Selects the type of torque limit setting. The torque limit can be set by using the keypad, analog<br />

input of the terminal block(V1, I1) or communication option.<br />

0 : Keypad-1, 1 : Keypad-2<br />

Sets the torque limit using the keypad. Up to 200% can be set on the basis of the rated torque of the motor and the limits<br />

on the rotation direction, reverse and regenerative limits are set in the following codes.<br />

CON-33 FWD +Trq Lmt : forward motoring operation torque limit<br />

CON-34 FWD –Trq Lmt : forward regeneration operation torque limit<br />

CON-35 REV +Trq Lmt : reverse motoring operation torque limit<br />

CON-36 REV –Trq Lmt : reverse regeneration operation torque limit<br />

2 : V1, 3 : I1<br />

The torque limit is set by using the analog input terminal of the inverter terminal block. The maximum torque is set by using<br />

IN-02 Torque at 100% item. For example, if IN-02 is set at 200% and voltage input(V1) is used, the torque limit is 200%<br />

when 10V is input(only when the V1 terminal function is set at the default function). When the torque limit setting method is<br />

other than the keypad, the set value is confirmed in the monitor mode. No. 20 Torque Limit is selected in Config Mode<br />

CNF-06~08.<br />

3 : Int 485<br />

Sets the torque limit using the communication terminal of the inverter terminal block.<br />

Torque Bias Setting<br />

CON-58 Trq Bias Src : Selects the type of setting of the offset value added to the torque reference.<br />

0 : Keypad-1, 1 : Keypad-2<br />

Setting by using the keypad is input in CON-38 Torque Bias. up to 120% of the rated current of the motor can be set.<br />

2 : V1, 3 : I1, 6 : Int 485<br />

The setting method is the same as the torque reference described above. The setting can be checked in MON mode and<br />

select No. 21 Torque Bias among CNF-06 ~ 08.<br />

8-30