Setting Items Functions<br />

bit2 bit1 On the far right of the display is bit 1.<br />

� Selects output phase open protective action.<br />

� Selects input phase open protective action.<br />

� � Selects input/output phase open protective action.<br />

01 : Output phase open protection<br />

Chapter 10 Protective Functions<br />

In case of phase open of one or more phase of U, V, W of the inverter output terminal block, the inverter blocks output and<br />

displays Out Phase Open.<br />

10 : Input phase open protection<br />

In case of phase open of one or more phase of R, S, T of the inverter input terminal block, the inverter blocks output and<br />

displays In Phase Open on the keypad. Protection against input phase open starts only when a certain amount of<br />

current(70~80% of the inverter rated output current) flows through the motor.<br />

PRT-06 : IPO V Band : In case of phase open of one or more phase of the inverter inputs, the ripple of the DC link<br />

voltage gets too large. The band of the ripple voltage is set. If the band of the ripple voltage set in this function code is<br />

exceeded, input phase open trip occurs.<br />

Note<br />

Make sure that you set the motor rated current (BAS-13 Rated Curr) rightly. If the motor rated current being actually<br />

used differs from the value set at BAS-13, phase open protection might fail to operate.<br />

10.1.6 External failure signal<br />

Group Code No. Function Display Setting Display Unit<br />

IN<br />

65~75 Px Define 4 External Trip -<br />

87 DI NC/NO Sel - 000 0000000 -<br />

By using No. 4 External Trip(external failure) among the multi-function input terminal functions, you can stop the<br />

inverter operating in case of a problem with the system.<br />

IN-87 DI NC/NO Sel : You can select the type of the input contact point. If the Dot mark of the switch is at the bottom, it<br />

is A contact point(Normal Open) and if at the top, it operates as B contact point(Normal Closed). The terminals of each<br />

bit are as follows.<br />

bit<br />

Multi—<br />

11 10 9 8 7 6 5 4 3 2 1<br />

function<br />

terminal<br />

P8 P7 P6 P5 P4 P3 P2 P1<br />

10-8