Chapter 9 Monitor Functions<br />

9-2<br />

Setting Function<br />

terminal of the inverter terminal block.<br />

12 I1 Monitor[%]<br />

Displays the current above in percentage. If the input<br />

current is 0~20[mA], it is represented by 0~100%.<br />

13 V2 Monitor[V]<br />

Displays the voltage input of the V2 terminal of the I/O<br />

option card when you use the extended I/O option.<br />

14 V2 Monitor[%] Displays the V2 input voltage in percentage.<br />

15 I2 Monitor[mA]<br />

The current input into the I2 terminal of the I/O option<br />

card when you use the extended I/O option.<br />

16 I2 Monitor[%]<br />

Displays the input current of the I2 terminal in<br />

percentage.<br />

17 PID Output Displays the output of the PID controller.<br />

18 PID Ref Value Displays the reference of the PID controller.<br />

19 PID Fdb Value Displays the feedback of PID controller.<br />

If the torque reference command method (DRV-08) is set<br />

20 Torque<br />

as methods other than the keypad (0 or 1), the torque<br />

reference is displayed.<br />

If the torque limit setting method (CON-53) is set as<br />

21 Torque Limit methods other than the keypad (0 or 1), the torque limit is<br />

displayed.<br />

If the torque bias setting method (CON-58) is set as<br />

22 Trq Bias Ref methods other than the keypad (0 or 1), the torque bias is<br />

displayed.<br />

If the speed limiting method (CON-62) in the torque<br />

23 Spd Limit<br />

control mode is set as methods other than the keypad (0<br />

or 1), the speed limit amount is displayed.<br />

Displays the load speed in the scale and unit which the<br />

user wants. Displays the load speed in the values to<br />

24 Load Speed which ADV61 (Load Spd Gain) and ADV62 (Load Spd<br />

Scale) are applied in the units of rpm or mpm set in<br />

ADV63 (Load Spd Unit).<br />

2) Output power display<br />

Mode Group Code No.<br />

PAR BAS 18<br />

Function<br />

Display<br />

Trim<br />

Power %<br />

Initial Setting Unit<br />

- 100.0 %<br />

BAS-18 Trim Power % : selects No. 4 Output Power among the monitor items described above, raises this set<br />

value properly when the output power displayed in the loader is lower than expected. If the output power displayed in<br />

the loader is higher than expected, it decreases this set value properly. Output power display is calculated with<br />

voltage and current and Output power can have a error when power factor is low.