Chapter 7 Basic Functions<br />

ADV-03 Acc S Start: You can adjust the slope of the curve when you set the Acc/Dec pattern as S-curve. This is used<br />

to adjust the curvilinear ratio of S-curve when acceleration begins. The curve ratio sets the ratio of the curve<br />

acceleration of the 1/2 frequency on the basis of a half of the target frequency. For example, if ADV-03 Acc S Start is<br />

set at 50% and the target frequency, which equals the maximum frequency(m[Hz]ax Freq), is 60Hz, the frequency<br />

which the curve acceleration accounts for when the S-curve accelerates to 30Hz is 0~15Hz and the 15Hz~30Hz<br />

interval is linear acceleration.<br />

ADV-04 Acc S End: You can adjust the slope of the curve when the operating frequency reaches the target<br />

frequency. This is used to set the ratio accounted for by the curve acceleration of the remaining interval on the basis of<br />

the 1/2 frequency of the target frequency as in case of Acc S Start. If set as in Acc S Start above, it accelerates in a<br />

linear slope until 30~45Hz and then accelerates in a curve slope and operates at a steady speed for the remaining<br />

45~60Hz interval.<br />

Frequency<br />

Operating<br />

Command<br />

Linear<br />

Acc Time Dec Time<br />

ADV-05 Dec S Start ~ ADV-06 Dec S End: Sets the curve deceleration slope ratio during deceleration. The setting<br />

method is as the acceleration ratio described above.<br />

S-Curve<br />

Acc/Dec Time in S-curve:<br />

Acc Time = Set Acc Time + Set Acc Time x (ADV-03)/2 + Set Acc Time x (ADV-04)/2<br />

Dec Time = Set Dec Time + Set Dec Time x (ADV-05)/2 + Set Dec Time x (ADV-06)/2<br />

Max Freq<br />

Out Freq<br />

(Hz)<br />

Variation of Delta<br />

Frequency<br />

Linear<br />

Sstart Send<br />

Linear<br />

Sstart Send<br />

[ S-Curve Acc/Dec Pattern ]<br />

Max Freq/2<br />

Time(sec)<br />

Time(sec)<br />