Chapter 8 Applied Functions<br />

8.1.25 Input power frequency selection<br />

8-44<br />

Group Code No. Function Display Initial Setting Display Unit<br />

BAS 10 60/50 Hz Sel 0 60 Hz<br />

Select the inverter input power frequency.<br />

If changed from 60Hz to 50Hz, the items related to the frequency(or rpm) set higher than 60Hz are all changed into<br />

50Hz.<br />

If changed from 50Hz to 60Hz, the items related to the frequency(or rpm) set higher than 50Hz are all changed into<br />

60Hz.<br />

8.1.26 <strong>Inverter</strong> input voltage selection<br />

Group Code No. Function Display Initial Setting Display Unit<br />

BAS 19 AC Input Volt - 220 V<br />

Sets the inverter input power voltage. The low voltage failure(Low Voltage) automatically changes on the basis of<br />

the set voltage.<br />

8.1.27 Parameter writing and reading<br />

Group Code No. Function Display Setting Display Unit<br />

46 Parameter Read 1 Yes -<br />

CNF 47 Parameter Write 1 Yes -<br />

48 Parameter Save 1 Yes -<br />

This is the function of copying the parameter saved in the inverter to the keypad and copying the parameter saved<br />

in the keypad to the inverter.<br />

CNF-46 Parameter Read : Copies the parameter in the inverter to the keypad. The existing parameters saved in<br />

the keypad are all deleted.<br />

CNF-47 Parameter Write : Copies the parameter saved in the keypad to the inverter. The existing parameters in<br />

the inverter are all deleted. In case of an error during parameter writing motion, the previously saved data can be<br />

directly used. If there is no data saved in the keypad, a message reading “ EEP Rom Empty “ is displayed.<br />

CNF-48 Parameter Save : Because the parameters set in communication are saved in the RAM area, they are all<br />

gone if the inverter power is turned Off/On. If you set parameters in communication and select Yes in CNF-48<br />

Parameter Save, the set parameters remain unchanged even if the inverter power is turned Off/On.