9.1 Monitor Functions<br />

9.1.1 Monitor in operation - Keypad<br />

Chapter 9 Monitor Functions<br />

You can monitor the operating status using the keypad of the inverter. You can select the desired items to monitor in<br />

the config mode(CNF), watch three items at a time in the monitor mode and select an item in the status display.<br />

1) Selection of Monitor Mode Display<br />

Mode Group Code No.<br />

Function<br />

Display<br />

Initial Setting Unit<br />

- 21 Monitor Line-1 0 Frequency Hz<br />

CNF<br />

-<br />

-<br />

22<br />

23<br />

Monitor Line-2<br />

Monitor Line-3<br />

2<br />

3<br />

Output Current<br />

Output Voltage<br />

A<br />

V<br />

24 Mon Mode Init 0 No -<br />

CNF-21~23 Monitor Line-x : Selects the items to display in the monitor mode. Monitor mode is displayed first when<br />

the power is supplied and all three items of Monitor Line-1 ~ Monitor Line-3 can be displayed simultaneously.<br />

Choose from the following items suited to the line you want to display. If you choose Yes in CNF-24 Mon Mode Init,<br />

CNF-21~23 is initialized.<br />

Setting Function<br />

During stop, the set frequency is displayed and during<br />

0 Frequency operation, the currently output operating frequency is<br />

displayed in Hz unit.<br />

1 Speed The same as above(0) and displayed in rpm unit.<br />

2 Output Current Displays the magnitude of the output current.<br />

3 Output Voltage Displays the output voltage.<br />

4 Output Power Displays the output power.<br />

5<br />

WHour<br />

Counter<br />

Displays the electricity consumed by the inverter.<br />

Displays the DC power voltage inside the inverter. During<br />

6 DCLink Voltage stop, it represents the maximum value of the DC input<br />

voltage.<br />

Displays the status of the input terminals of the inverter<br />

7 DI Status<br />

terminal blocks. From the right, they are represented by<br />

P1,P2…P11.<br />

Displays the status of the output terminals of the inverter<br />

8 DO Status terminal blocks. From the right, they are represented by<br />

Relay1, Relay2, Q1.<br />

9 V1 Monitor[V]<br />

Displays the values being input into V1, the voltage input<br />

terminal of the inverter terminal block in the voltage term.<br />

10 V1 Monitor[%]<br />

Displays the voltage unit above in percentage. If -10 ~ 0<br />

~ +10V is input, it is represented by -100 ~ 0 ~ 100%.<br />

11 I1 Monitor[mA] Displays the magnitude of the current being input into I1<br />

9-1