Chapter 9 Monitor Functions<br />

9.1.5 Failure status output by relay and Multi-function output terminal of terminal block<br />

The inverter failure status can be output using the multi-function output terminal(Q1) and relay(relay 1 and 2).<br />

9-16<br />

Group<br />

OUT<br />

Code<br />

No.<br />

Function<br />

Display<br />

30 Trip Out Mode - 010<br />

Initial Setting Unit<br />

31 Relay 1 29 Trip -<br />

32 Relay 2 14 Run -<br />

33 Q1 Define 1 FDT-1 -<br />

53 TripOut On Dly - 0.00 Sec<br />

54 TripOut OffDly - 0.00 sec<br />

*The inverter failure status can be output by added OUT 34~36 when extended I/O is mounted.<br />

OUT-30 Trip Out Mode : Select the No. 28 Trip Mode at OUT-31~33 after selecting the terminal and relay to use for<br />

failure output. The terminal and relay gets active in case of a failure of the inverter. The activeness can be set as<br />

follows according to the type of the failure.<br />

Setting Item Function<br />

bit3 bit2 bit1 Bit 1 is on the right of the display.<br />

� Active in case of Low Voltage failure<br />

� Active in case of a failure due to other than low voltage<br />

� Active in case of auto re-start failure(PRT-08, PRT-09)<br />

OUT-53 TripOut On Dly, OUT-54 TripOut OffDly : The failure relay or multi-function output becomes active after the<br />

period of time set in OUT-53 in case of a failure. With reset input, the contact point gets OFF after the period of time<br />

set in OUT-54.