Chapter 9 Monitor Functions<br />

2) Failure History Monitor<br />

Types of up to five previous failures can be saved and monitored. The lower the number of Last X is, the more recent<br />

failure it represents. If more than 5 failures have occurred, those that occurred before the last 5 ones are<br />

automatically deleted.<br />

The items displayed in the failure history are as follows.<br />

9-6<br />

Displayed Information Function<br />

0 Trip Names(1) Displays the type of the failure<br />

1 Output Freq<br />

The operating frequency at the time of<br />

the failure<br />

2 Output Current<br />

The output current at the time of the<br />

failure<br />

3 <strong>Inverter</strong> State<br />

Displays acceleration, deceleration,<br />

steady speed operation and stop<br />

4 DCLink Voltage <strong>Inverter</strong> DC power voltage<br />

5 Temperature <strong>Inverter</strong> temperature<br />

6 Input State Displays the input terminal status<br />

7 Output State Displays the output terminal status<br />

8 Trip On Time<br />

Displays the time from the inverter<br />

power ON to the failure<br />

9 Trip Run Time<br />

Displays the time from the inverter Run<br />

to the failure<br />

10 Trip Delete ?<br />

Displays whether the currently saved<br />

failure history is to be deleted<br />

There are two ways to delete the failure history. One is deleting each failure history by selecting Yes for Trip mode<br />

‘TRP-10 Trip Delete ?’ in the each failure history described above. The other is deleting all the failure history by<br />

selecting Yes for CNF-24 Erase All Trip of the Config Mode.