Chapter 7 Basic Functions<br />

If you set DRV-07 Freq Ref Src at Int 485, you can control the inverter through communication with the higher controller<br />

(PLC or PC) by using the RS485 (+S, -S) terminal of the terminal block. For details, see Communication Functions,<br />

Chapter 11.<br />

Note: Please refer to <strong>User</strong> manual for communication options such as Profibus, Device-net, and PLC options.<br />

7.1.2 Analog command frequency fixation<br />

Group Code No. Function Display Setting Displayed Setting Range Unit<br />

0 Keypad-1 0~9 -<br />

1 Keypad-2 0~9 -<br />

2 V1 0~9 -<br />

3 I1 0~9 -<br />

DRV 07 Freq Ref Src<br />

4<br />

5<br />

V2<br />

I2<br />

0~9<br />

0~9<br />

-<br />

-<br />

6 Int 485 0~9 -<br />

7 Encoder 0~9 -<br />

8 Fied Bus 0~9 -<br />

9 PLC 0~9 -<br />

IN 65~75 *Px Define 21 Analog Hold 65~75 -<br />

*Px : P1~P8, P9~P11 (option)<br />

This is the function of fixing the operating frequency when the terminal selected as the Analog Hold among the multi-<br />

function terminals if you set the frequency by using the analog input of the control terminal block.<br />

Set Frequency<br />

Frequency<br />

Px<br />

Operating Command<br />

7.1.3 Changing frequency to revolution<br />

If you set the Hz/Rpm Sel value at “1: Rpm Display, the frequency will change into revolution.<br />

Group Code No. Function Display Setting Displayed Setting Range Unit<br />

DRV 21 Hz/Rpm Sel 1 Rpm Display - rpm<br />