Chapter 8 Applied Functions<br />

If 10.4mA is being input into I1, the frequency corresponding to 20mA is 60Hz, so the auxiliary speed A in the table<br />

below is 24Hz(=60[Hz]x((10.4[mA]-4[mA])/(20[mA]-4[mA])) or 40%(=100[%]x((10.4[mA]-4[mA])/(20 [mA]-4[mA])).<br />

Setting Type Final Command Frequency<br />

0 M[Hz]+(G[%]*A[Hz]) 30Hz(M) + (50%(G) x 24Hz(A)) = 42Hz<br />

1 M[Hz]*(G[%]*A[%]) 30Hz(M)x(50%(G)x40%(A))=6Hz<br />

2 M[Hz]/(G[%]*A[%]) 30Hz(M)/(50%(G)x40%(A))=150Hz<br />

3 M[Hz]+(M[Hz]*(G[%]*A[%])) 30Hz(M)+(30[Hz]x(50%(G)x40%(A)))=36Hz<br />

4 M[Hz]+G[%]*2*(A[%]-50[%])[Hz] 30Hz(M)+50%(G)x2x(40%(A)–50%)x60Hz=24Hz<br />

5 M[HZ]*(G[%]*2*(A[%]-50[%])) 30Hz(M)x(50%(G)x2x(40%(A)–50%))= -3Hz (reverse)<br />

6 M[HZ]/(G[%]*2*(A[%]-50[%])) 30Hz(M)/(50%(G)x2x(60%–40%))= -300Hz (reverse)<br />

7 M[HZ]+M[HZ]*G[%]*2*(A[%]-50[%]) 30Hz(M)+30Hz(M)x50%(G)x2x (40%(A)–50%)= 27Hz<br />

8.1.2 Jog operation (If you want Jog operation)<br />

8-4<br />

Operation is also available using the terminal block and the multi keys of the keypad.<br />

1) Jog Operation by Terminal Block 1<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

DRV<br />

11 JOG Frequency - 10.00 0.5~maximum frequency -<br />

12 JOG Acc Time - 20.00 0~600 Sec<br />

13 JOG Dec Time - 30.00 0~600 Sec<br />

IN 65~75 Px Define 6 JOG - -<br />

*Px : P1~P8, P9~P11 (Option)<br />

Select the jog frequency setting terminal from the multi-function terminals P1 ~ P11 and set the function of the appropriate<br />

terminal block of IN-65 ~ IN-75 at No. 6 JOG. If the jog terminal which has been set with the operating command input, the<br />

operating frequency moves to the jog frequency, which is described below.<br />

DRV-11 Jog Frequency (Jog Frequency) : sets the frequency necessary for jog operation. Jog operation is the highest<br />

in the priority order except the dwell operation. Therefore, during sequential operation, up-down operation and 3-wire<br />

operation at a certain speed, if the jog terminal is input, it operates at the jog frequency.<br />

DRV-12 JOG Acc Time, DRV-13 JOG Dec Time : the deceleration and acceleration time during shift to jog frequency.