Chapter 10 Protective Functions<br />

10-7<br />

IN-65~75 Px Define, IN-82 DI NC/NO Sel : You can set the overheat trip function input by using the multi-function<br />

terminal block input when using bimetal type sensor relay. Connect PTC between the terminal block to use and CM<br />

and select No. 39 Thermal In among the function items. Select the type of contact point of the terminal used in IN-87<br />

as 1(NC).<br />

Using multi-function input terminal (Px)<br />

PRT-36 Thermal-T Lev : sets the action level of the motor overheat sensor. In case of voltage input terminal(V1), the<br />

maximum input voltage is 10V and in case of current(I1), the maximum input voltage is 5V. For example, if you use the<br />

current input terminal and set the failure level at 50%, the protective function gets active when the voltage supplied to<br />

the I1 terminal is below 2.5V. For how to operate it above 2.5V, see PRT-37 Thermal-T Area.<br />

PRT-37 Thermal-T Area : If voltage lower than the thermal failure level(PRT-36) when you set at No. 0 Low, the<br />

protective function becomes active and if No. 1 High, and if voltage higher than the failure level is input, the protective<br />

function starts.<br />

10.1.5 <strong>Inverter</strong> and sequence protection<br />

1) Input/Output phase open Protection<br />

The input phase open protection function is used to prevent over current through the inverter input terminal by input power phase<br />

open. If phase open occurs to the connection between the motor and inverter output, motor stall might happen due to torque<br />

insufficiency and that is why the output phase open protective function is used.<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

PRT<br />

I Px<br />

PTC<br />

05 Phase Loss Chk - 11 - Bit<br />

06 IPO V Band - 40 1~100V V<br />

You can select input and output phase open respectively. If the dot mark of the switch is at the top, it represents setting<br />

completed and if at the bottom, it does not operate (top:1, bottom:0).<br />

bit setting(ON) : bit setting canceled(OFF) :<br />