10.1.12 Speed variation failure<br />

This function is active when the control mode(DRV-09 Control Mode) is Vector.<br />

Group Code No. Function Display Setting Display Unit<br />

PRT<br />

73 Speed Dev Trip 1 Yes -<br />

74 Speed Dev Band - 20.00 Hz<br />

75 Speed Dev Time - 1.0 Sec<br />

Chapter 10 Protective Functions<br />

The inverter output is blocked when the motor rotates for the Speed Dev Time set at faster than the speed<br />

variation(Speed Dev Band).<br />

10.1.13 Speed sensor error detection<br />

It can be detected whether the encoder option card is mounted on the inverter main body. With the encoder mounted,<br />

an error is detected too when the encoder signal of the line drive method is a single line. In case of an error, a<br />

message reading Encoder Trip is displayed.<br />

Group Code No. Function Display Setting Display Unit<br />

PRT<br />

77 Enc Wire Check 1 Yes -<br />

78 Enc Check Time - 1.0 sec<br />

10.1.14 Fan failure detection<br />

Group Code No. Function Display Setting Display Unit<br />

PRT 79 FAN Trip Mode 0 Trip -<br />

OUT<br />

31~32 Relay 1,2 8 FAN Trip -<br />

33 Q1 Define<br />

If the cooling fan failure mode is set at No. 0 Trip and if a problem with the cooling fan is detected, the inverter output is<br />

blocked and the fan failure is displayed. If you set at No. 1 Warning and select No. 8 FAN Warning as the multi-function<br />

output terminal or relay, the fan failure signal is released and operation continues, However, if the temperature within<br />

the inverter rises above a certain degree, the output is blocked due to overheat of the cooling fan and so on.<br />

10.1.15 Selection of action in case of low voltage failure<br />

Group Code No. Function Display Setting Display Unit<br />

PRT 81 LVT Delay - 0.0 sec<br />

OUT<br />

31~32 Relay 1,2 11 Low Voltage -<br />

33 Q1 Define<br />

10-14