Chapter 8 Applied Functions<br />

APO-41 Aux Acc Time, APO-42 Aux Dec Time : The main motor stops PID control and normal acceleration and<br />

deceleration operation when the auxiliary motor runs or stops. When the auxiliary motor runs, the main motor<br />

decelerates to the decelerating frequency of the auxiliary motor for the decelerating time set at APO-42. Inversely,<br />

when the auxiliary motor stops, the main motor accelerates to the starting frequency for the accelerating time set at<br />

APO-41. For details on the PID control of the main motor, see page 8-12.<br />

2) Automatic Change of Motor(Auto Change)<br />

The motion sequence of the main and auxiliary motors can be automatically changed. If only a particular motor<br />

continues running, the life of the motor might be affected. Therefore the motion sequence can be reversed to keep<br />

the use time of the motors equal.<br />

APO-35 Auto Ch Mode : Selects the type of motions of the automatic change.<br />

0 : None<br />

The motion sequence of the auxiliary motor starts with the auxiliary motor selected in APO-21(starting auxiliary motor<br />

selection) and the automatic change function is not active.<br />

8-58<br />

Main<br />

motor<br />

output<br />

frequency<br />

Output<br />

terminal<br />

Main<br />

motor<br />

ouput<br />

frequency<br />

Output<br />

terminal<br />

Starting frequency of the<br />

auxiliary motor<br />

APO-23~26<br />

Stop delay time of the<br />

auxiliary motor<br />

APO-31<br />

auxiliary motor starts<br />

Starting frequency of the<br />

auxiliary motor<br />

APO-27~30<br />

Main motor acceleration time when the pump number increases<br />

APO-42<br />

stop sequence of the auxiliary motor following load increase<br />

Stop delay time of the<br />

auxiliary motor<br />

APO-32<br />

auxiliary motor stops<br />

Starting frequency of the<br />

auxiliary motor<br />

APO-23~26<br />

Stop frequency of the<br />

auxiliary motor<br />

APO-27~30<br />

Main motor acceleration time when the pump number decreases<br />

APO-41<br />

Stop sequence of the auxiliary motor following load<br />

decrease