Operating<br />

Command<br />

Frequency<br />

Chapter 7 Basic Functions<br />

7.1.20 Selection of second operating method (By-pass operation)<br />

You can enter the frequency, operating command and torque reference as the second set values by using the multi-<br />

function input terminal. This can be applied in case of remote operation using the communication option or operation<br />

in the main body of the inverter with the remote braking stopped.<br />

Group Code No. Function Display Setting Display Unit<br />

06 Cmd Source 1 Fx/Rx-1 -<br />

DRV 07 Freq Ref Src 2 V1 -<br />

08 Trq Ref Src 0 Keypad-1 -<br />

04 Cmd 2 nd Src 0 Keypad -<br />

BAS 05 Freq 2nd Src 0 KeyPad-1 -<br />

06 Trq 2 nd Src 0 Keypd-1 -<br />

IN 65~75 Px Define 15 2nd Source -<br />

Select one of the multi-function terminals between IN-65 ~ IN-75 of the terminal block input group.<br />

BAS-04 Cmd 2nd Src, BAS-05 Freq 2nd Src: With the multi-function input terminal set as 2nd Source ON, the<br />

inverter can operate with the values set at BAS-04 and 05 instead of the values set at DRV-06 and DRV-07.<br />

BAS-06 Trq 2nd Src: With the multi-function input terminal ON, you can enter the torque reference in the method<br />

selected in BAS-06 instead of the method chosen in DRV-08. DRV-08 and BAS-06 are displayed only after the control<br />

mode(DRV-09) is set as sensorless vector or vector control mode and the torque mode(DRV-10) is set as Yes.<br />

Caution<br />

With the multi-function input terminal set as the 2 nd source and turned ON, the operation status<br />

changes because the frequency command, operating command and torque reference all turn into<br />

2 nd commands. Therefore make sure you check whether 2 nd commands are rightly set before<br />

inputting the multi-function terminal.<br />

ADV-33<br />

ADV-32<br />

ADV-31<br />

ADV-30<br />

ADV-29<br />

ADV-28<br />

10V<br />

V1<br />

(Voltage Input)<br />

0 20mA I (Current Input)<br />

: Frequency<br />

Declining<br />

: Frequency<br />

Rising<br />

7-30