Chapter 11 Communication Function<br />

11-2<br />

11.1.2 Specifications<br />

Category Specifications<br />

Communication method RS-485<br />

Transfer form Bus type, Multi drop Link System<br />

<strong>Inverter</strong> series <strong>SV</strong>-<strong>iS7</strong> series<br />

Converter Embedded with RS-232<br />

Number of connected<br />

inverters<br />

Max. 16<br />

Transfer distance Max. 1,200m (recommend within 700m)<br />

Recommended cable for<br />

communication<br />

0.75mm 2 (18AWG), Shield Type Twisted-Pare Wire<br />

Installation form Connect to S+,S-, CM of the terminal block<br />

Communication Power<br />

Use the power that are insulated from the inner part of inverter as<br />

communication power(supplied from inverter)<br />

Communication Speed Select out of 1,200/2,400/9,600/19,200/38,400 bps<br />

Control procedure Unsynchronized communication system<br />

Communication system Half duplex system<br />

Letter system Modbus-RTU: BINARY LS Bus: ASCII<br />

Stop bit length 1 bit/2 bit<br />

Sum check 2 byte<br />

Parity check None/Even/Odd<br />

11.1.3 Composition of communication system<br />

PC<br />

RS-485 terminal connection: connect to S+, S- of the terminal block (see Chapter 4 Wiring)<br />

Number of connectable inverters: up to 16 units<br />

Number of extendable addresses(St ID):1~250<br />

Length of effective communication lines: possibly 1200m in total. Keep it below 700m for stable communication.<br />

Please use communication Repeater to enhance the communication speed if you have to use communication cable<br />

above 1200m or to connect additional inverter. It is effective to reduce the noise influence from communication by<br />