9.1.6 Output terminal delay time and type of contact point<br />

Chapter 9 Monitor Functions<br />

The output terminal of the terminal block and the operating time of the relay can be adjusted. ON and OFF delay<br />

time can be separately set and you can choose between A contact point(Normal Open) and B contact point(Normal<br />

Closed).<br />

1) Output Terminal Delay Time<br />

Group<br />

Code<br />

No.<br />

Function<br />

Display<br />

Initial Setting Unit<br />

OUT<br />

50<br />

51<br />

DO On Delay<br />

DO Off Delay<br />

-<br />

-<br />

0.00<br />

0.00<br />

Sec<br />

Sec<br />

Operates as follows if OUT-32 Relay 2 is set as No.14 Run and ON delay time(DO On Delay) and OFF delay<br />

time(DO Off Delay) are set at 1 sec and 2 sec respectively.<br />

The delay time set at OUT-50 and 51 apply to both the multi-function output terminal(Q1) and relay(Relay 1,2)<br />

except for failure mode of the multi-function output function.<br />

2) Selection of Type of Output Signal Contact Point<br />

Group<br />

Code<br />

No.<br />

Function<br />

Display<br />

Initial Setting Unit<br />

OUT 52 DO NC/NO Sel 000 bit<br />

Selects the type of the contact point of the relay and multi-function output terminal. If extended I/O is mounted, the<br />

selecting 3 of bits for contact point type of terminal block will be added. If the appropriate bit is set at 0, it operates as<br />

A contact point(NO) and if at 1, it operates as B contact point(NC). From the right bit, Relay1, Relay 2, Q1, Relay 3,<br />

Relay 4, Relay 5.<br />

9.1.7 Operating time monitor<br />

Group<br />

CNF<br />

Code<br />

No.<br />

Function<br />

Display<br />

Initial Setting Unit<br />

70 On-time - 0/01/01 00:00 min<br />

71 Run-time - 0/01/01 00:00 min<br />

72 Time Reset 0 No -<br />

74 Fan time - 0/00/00 00:00 min<br />

75<br />

Fan<br />

Reset<br />

Time<br />

0 No -<br />

CNF-70 On-time : time is accumulated with the inverter supplied with power. The information on the display is as<br />

follows.<br />

yy:mm(month):dd:hh:mm(minute)<br />

0 / 00 / 00 00 : 00<br />

9-17