7.1.21 Multi-function input terminal control<br />

(Improving responsiveness of input terminal)<br />

Chapter 7 Basic Functions<br />

You can set the filter time constant and contact point type for the multi-function input terminal of the inverter terminal<br />

Group Code No. Function Display Setting Display Setting Range Unit<br />

IN<br />

85 DI On Delay - 0 0~10000 msec<br />

86 DI Off Delay - 0 0~10000 msec<br />

87 DI NC/NO Sel - 0000 0000 - -<br />

90 DI Status - 0000 0000 - -<br />

1) IN-85 DI On Delay, IN-86 DI Off Delay: If the state of the input terminal does not change for a set period of time<br />

after the terminal input, it is identified as ON or OFF.<br />

2) IN-87 DI NC/NO Sel: The type of contact point of the input terminal can be selected. If you set the place of the dot<br />

of the switch corresponding to each bit below, you can use it as A contact point(Normal Open) and if above, you can<br />

use it as B contact point(Normal Close). The order is P1, P2…P8 from the right. Digital input will be added when<br />

extended I/O is used so DINC/NO Sel 3 bits will be added. From the right, status of P1, P2, …, P11.<br />

3) IN-90 DI Status: displays the status of the input terminal block. If extended I/O used, status display bit of input<br />

terminal block will be added 3 bits. If the appropriate bit is set at A contact point in DRV-82, ON is displayed when the<br />

Dot is above and OFF is displayed when below. If the appropriate bit is set at B contact point, it operates reversely.<br />

From the right, status of P1, P2…P11 is shown.<br />

7.1.22 Digital input and output control by extended I/O option card<br />

If you mount an extended I/O card on the inverter option slot, you can use additional 3 digital inputs and 3 digital<br />

outputs (relay output).<br />

Group Code No. Function Display Setting Display Unit<br />

73 P9 Define 0 None -<br />

IN 74 P10 Define 0 None -<br />

75 P11 Define 0 None -<br />

34 Relay 3 2 FDT-2<br />

OUT 35 Relay 4 3 FDT-3<br />

36 Relay 4 4 FDT-4<br />

7-31